4.3 SEALING THE METER

Once commissioning is complete install the two security seals provided with the meter
as shown below.

5.0: DIAGNOSTIC FUNCTIONS

The ONICON System-40 has self diagnostic functions that continually monitor key
operating parameters. A list of the alarm messages is shown below.

Displayed Message

Description

System Fault

System Fault is displayed with an error code. This message
indicates a hardware malfunction. The meter will not
calculate energy in this state.

Reverse Flow

Flow is reversed through the meter. The meter will not
calculate energy in this state.

Signal Fault

This is a warning message that the flow signal is weak. It may
indicate entrained air in the flow stream.

Dt< Minimum

This is a warning message that the delta temperature is low.

Empty Pipe

The pipe is empty.

Flow RTD Open

The temperature sensor in the flow body is reading open.
The meter will not calculate energy in this state.

Flow RTD Short

The temperature sensor in the flow body is reading as a short
circuit. The meter will not calculate energy in this state.

Remote RTD Open

The remote temperature sensor is reading open. The meter
will not calculate energy in this state.

Remote RTD Short

The remote temperature sensor is reading as a short circuit.
The meter will not calculate energy in this state.

Low Flow

The flow reading is below the minimum flow threshold of
the meter (e.g. 0.03 gpm for ½” meter). The meter will not
calculate energy in this state.

High Flow

This is a warning message that the flow reading is above the
maximum flow rate of the meter (e.g. 15 gpm for ½” meter).

Security Seals