ONICON System-40-BAC BTU User Manual
Page 25

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
System-40-BAC BTU Meter Manual 03/15 - 1045-2
Page
25
6.8
TREND LOG MULTIPLE
Property
Default Value
Read-only or
Writable
Comment
Object Identifier
Trend-log-multiple,1
Read-only
Object Name
Log Data
Read-only
Object Type
Trend-log-multiple
Read-only
Description
Trend-log-multiple,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
normal
Read-only
Reliability
No-fault-detected
Read-only
Enable
TRUE
Writable
Log Device Property
Read-only
See Note Below
Logging Type
POLLED
Read-only
Log Interval
9000
Writable
Stop When Full
FALSE
Read-only
Buffer Size
480
Read-only
Log Buffer
Read-only
Record Count
0
Writable
Total Record Count
0
Read-only
Note: Log Device Property – Log intervals can be set over a range of 30 seconds to 60
minutes. The following objects can be logged:
Analog-input, 1
Energy Rate
Analog-input, 2
Volume Rate
Analog-input, 3
Supply Temperature
Analog-input, 4
Return Temperature
Analog-input, 5
Delta Temperature
Analog-value, 1
Volume Total Mode 1
Analog-input, 2
Volume Total Mode 2
Analog-value, 9
Volume Total Mode 1
Analog-input, 10
Volume Total Mode 2
Multi-state-value, 1
Meter Status