6.3

DEVICE OBJECT

Property

Default Value

Read-only or

Writable

Comment

Object Identifier

57017

Writable

0-4,194,303

Object Name

System-40-XXXXXX

Read-only

Object Type

Device

Read-only

System Status

Operational

Read-only

Vendor Name

ONICON Inc.

Read-only

Model Name

System-40-BAC

Read-only

Firmware Rev.

000.000.000

Read-only

Location

Customer Location

Writable

32 char. Max

Description

Customer Description

Writable

32 char. Max

Protocol Version

1

Read-only

Protocol Revision

10

Read-only

Services Supported

Read property, Read property
multiple, Write property, Write
property multiple, Read range,
Who-has, I have, Who-is, I-am,
Device communications control,
Time synchronization, UTC time
synchronization

Read-only

Object Types Supported Analog input, Analog value, Binary

input, Device, Multi-state value,
Trend log multiple

Read-only

Object List

(Device, 57017), (analog input, 1 –
10), (analog value, 1 – 22), (binary
value, 1 – 10), (trend log multiple,
1), (multi state value, 1)

Read-only

Max ADPU Length

480

Read-only

Local Time

Device current time

Read-only

Local Date

Device current date

Read-only

UTC Offset

-300

Writable

Daylight Savings Status

False

Writable

APDU Timeout

6000

Read-only

# of APDU Retries

3

Writable

Max Master

127

Read-only

Device Address Binding

Read-only

Active

Database Revision

1

Read-only