6.3
DEVICE OBJECT
Property
Default Value
Read-only or
Writable
Comment
Object Identifier
57017
Writable
0-4,194,303
Object Name
System-40-XXXXXX
Read-only
Object Type
Device
Read-only
System Status
Operational
Read-only
Vendor Name
ONICON Inc.
Read-only
Model Name
System-40-BAC
Read-only
Firmware Rev.
000.000.000
Read-only
Location
Customer Location
Writable
32 char. Max
Description
Customer Description
Writable
32 char. Max
Protocol Version
1
Read-only
Protocol Revision
10
Read-only
Services Supported
Read property, Read property
multiple, Write property, Write
property multiple, Read range,
Who-has, I have, Who-is, I-am,
Device communications control,
Time synchronization, UTC time
synchronization
Read-only
Object Types Supported Analog input, Analog value, Binary
input, Device, Multi-state value,
Trend log multiple
Read-only
Object List
(Device, 57017), (analog input, 1 –
10), (analog value, 1 – 22), (binary
value, 1 – 10), (trend log multiple,
1), (multi state value, 1)
Read-only
Max ADPU Length
480
Read-only
Local Time
Device current time
Read-only
Local Date
Device current date
Read-only
UTC Offset
-300
Writable
Daylight Savings Status
False
Writable
APDU Timeout
6000
Read-only
# of APDU Retries
3
Writable
Max Master
127
Read-only
Device Address Binding
Read-only
Active
Database Revision
1