ONICON System-40-BAC BTU User Manual
Page 23

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
System-40-BAC BTU Meter Manual 03/15 - 1045-2
Page
23
6.4
ANALOG INPUT(S)
Property
Default Value
Read-only or
Writable
Comment
Object Identifier
Analog-input,1 to analog-input,10
Read-only
Object Name
Various
Read-only
Object Type
Analog-input
Read-only
Present Value
REAL
Writable
Description
Analog-input,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
normal
Read-only
Reliability
No-fault-detected
Read-only
Out-of-Service
FALSE
Writable
Update interval
100
Read-only
Units
Various
Read-only
Min-Present-Value
-1000000000
Read-only
Max-Present-Value
1000000000
Read-only
Resolution
0.000001
Read-only
6.5
ANALOG VALUE(S)
Property
Default Value
Read-only or
Writable
Comment
Object Identifier
Analog-value,1 to analog-value,22
Read-only
Object Name
Various
Read-only
Object Type
Analog-value
Read-only
Present Value
REAL
Writable
Description
Analog-value,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
normal
Read-only
Reliability
No-fault-detected
Read-only
Out-of-Service
FALSE
Writable
Units
Various
Read-only
Priority Array
{NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL}
Read-only
Relinquish Default
0
Read-only