beautypg.com

ONICON System-40-BAC BTU User Manual

Page 24

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]

System-40-BAC BTU Meter Manual 03/15 - 1045-2

Page

24

6.6

BINARY VALUE(S)

Property

Default Value

Read-only or

Writable

Comment

Object Identifier

Binary-value,1 to binary-value,10

Read-only

Object Name

Various

Read-only

Object Type

Binary-value

Read-only

Present Value

0

Writable

Description

Binary-value,# Name

Read-only

Status Flags

(F,F,F,F)

Read-only

Event State

normal

Read-only

Reliability

No-fault-detected

Read-only

Out-of-Service

FALSE

Writable

Elapsed Active Time

Various

Read-only

Priority Array

(NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL)

Read-only

Relinquish Default

0

Read-only

6.7

MULTI STATE VALUE

Property

Default Value

Read-only or

Writable

Comment

Object Identifier

Multi-state-value,1

Read-only

Object Name

Meter Status

Read-only

Object Type

multi-state-value

Read-only

Present Value

1

Writable

Description

Multi-state-value,# Name

Read-only

Status Flags

(F,F,F,F)

Read-only

Event State

normal

Read-only

Reliability

No-fault-detected

Read-only

Out-of-Service

FALSE

Writable

Number of States

11

Read-only

State Text

Normal, Low Supply Temperature,
High Supply Temperature, Low
Return Temperature, Delta T<
Minimum, High Energy Rate, Low
Signal Quality, Comm Error, Low
Supply Voltage, System Fault

Read-only

Relinquish Default

0

Read-only