ONICON System-40-BAC BTU User Manual
Page 24
11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax +1 (727) 442-5699 • [email protected]
System-40-BAC BTU Meter Manual 03/15 - 1045-2
Page
24
6.6
BINARY VALUE(S)
Property
Default Value
Read-only or
Writable
Comment
Object Identifier
Binary-value,1 to binary-value,10
Read-only
Object Name
Various
Read-only
Object Type
Binary-value
Read-only
Present Value
0
Writable
Description
Binary-value,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
normal
Read-only
Reliability
No-fault-detected
Read-only
Out-of-Service
FALSE
Writable
Elapsed Active Time
Various
Read-only
Priority Array
(NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL,
NULL, NULL)
Read-only
Relinquish Default
0
Read-only
6.7
MULTI STATE VALUE
Property
Default Value
Read-only or
Writable
Comment
Object Identifier
Multi-state-value,1
Read-only
Object Name
Meter Status
Read-only
Object Type
multi-state-value
Read-only
Present Value
1
Writable
Description
Multi-state-value,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
normal
Read-only
Reliability
No-fault-detected
Read-only
Out-of-Service
FALSE
Writable
Number of States
11
Read-only
State Text
Normal, Low Supply Temperature,
High Supply Temperature, Low
Return Temperature, Delta T<
Minimum, High Energy Rate, Low
Signal Quality, Comm Error, Low
Supply Voltage, System Fault
Read-only
Relinquish Default
0
Read-only