8.1 Atomiser
BS5/10
BS 5
BS 10
Capacity 5
kg/h
(11lbs/h)*
10
kg/h
(22lbs/h)*
Compressed air requirements
30 Nlm
60 Nlm
Working pressure air / water
3-4 bar/0.2-0.4 bar
43-58psi/2.9-5.9psi
*
1
Dimensions (w x h x d) in inches
8.26 x 21.7 x 9.84
Weight Approx.
6.06
pounds
Operating voltage
48 VAC, 60 Hz, ±10%
Power input
20W
Overvoltage category
II
Pollution degree
2
Application Only
inside
Height above sea level
2,000 m (6670 ft)
Ambient temperature
7-35°C (45-95°F)
Ambient humidity
Max. 80 %, prevent condensation
*:
Depending on the set water / air ratio
*
1
: factory settings
9. Annex
9.1 Accessories/spare
parts
Position No of the article
Designation of the article
1 AF-Z-90
Cutter
2 004017
Filter
5