7. Exchange

of

components


Please notify NORTEC Service if you find a fault in the system.

If there is a question please call +1 613 822 0335.

The exchange is to be made only by instructed, trained personnel. The operator is obliged to make sure
that the personnel is suited, has been instructed and trained as required. He is obligated to comply the
instructions of DRAABE in the process, especially the instructions contained in this documentation.

CAUTION:
Please inform the people working nearby that works will be carried out on the air humidification
system. Make sure that the system cannot be switched on unintentionally.


7.1

Atomiser BS5/10

1. Close the shut-off valves (1) on the wall bracket.

2. Pull off the plug couplings (2) and (3) for compressed air and water. Press down the knurled ring

and then pull out the plug couplings downwards in order to do that.


3. Pull off the plug (4). Loosen the knurled ring on the plug by turning it anti-clockwise and pull out

the plug downwards for that purpose.


4. Remove the atomiser by unscrewing the star knob screw (5) and attach the new atomiser.

5. Connect the new atomiser in reverse order (do not connect the supplying lines crosswise!) Set

the desired set point, for example 50% r. h.) on the hygrostat. Adjust the atomiser by means of
the star knob screw (5).