4.2.1.3 Determining the compressed air and water requirements

Compressed air requirements


The compressed air consumption of a system depends on the number of atomisers.
BS5:

30 Nl/min

BS10:

60 Nl/min


Related to the example and using the following values:

Area 1 = 660 Nl/min
Area 2 = 120 Nl/min
The result is an air volume of 780 Nl/min

NOTE:
In order to ensure a trouble-free operation, the compressed air system ought to deliver 1.2 times
the air volume that has been calculated.

Water requirements


The water consumption of a system depends on the number of atomisers.


BS5

5 l/h (11 lbs/h)

BS10

10l/h

(22

lbs/h)

Related to the example and using the following values:
Area 1 = 110 l/h (243 lbs/h)

Area 2 = 20 l/h (44 lbs/h)

The result is an air volume of 130 l/h (287 lbs/h).

NOTE:
In order to ensure a trouble-free operation, the water system ought to deliver 1.2 times the maximum
water volume that has been calculated.