4.1.1.3 Determining the compressed air and water requirements

Compressed air requirements

The compressed-air consumption of a system depends on the number of atomisers and is calculated
using the following formula:

Q

L

= n

D

* 60Nl/min

BS10

30Nl/min

BS5


Q

L

: Necessary air volume in Nl/min

n

D

: Number of devices

Related to the example and using the following values:

n

D

= 5


The result is an air volume of 300 l/min.

NOTE:
In order to ensure a trouble-free operation, the compressed-air system ought to deliver 1.2 times
the air volume that has been calculated.

Water requirements


The water requirements of a system depend on the number of atomiser and is calculated using
the following
formula:

Q

W

= n

D

x 10l/h

Q

W

:

Necessary water in l/h

n

D

:

number of devices

Related to the example and using the following values

:

n

D

= 5

The result is a water volume of 50 l/h (110.5 lbs/h).

NOTE:
In order to ensure a trouble-free operation, the water system ought to deliver 1.2 times the
maximum water volume that has been calculated.