Installation, B. vertical (through-the-roof) installations, Vent restrictors – Montigo C42DV User Manual

Page 8

background image

Page 8

C42-DV Gas Fireplace

®

Part No. XG0119C

Part

Size

5/8 Venting 4/7 Venting

A - Termination

n/a

PVTK-1

MVTK-1

B - Flex sections

12

PFL-1

MFL-1

24

PFL-2

MFL-2

36

PFL-3

MFL-3

48

PFL-4

MFL-4

C - Solid sections

12

EXT-1

MEXT-1

24

EXT-2

MEXT-2

36

EXT-3

MEXT-3

48

EXT-4

MEXT-4

D - Support Ring

& Plate

PSPXT-8

MSPXT-7

E - Firestop

PS-8

FS-7

F - Roof Flashing

(1/12 - 7/12 pt.)

PRF-7

MRF-7

(7/12 - 12/12 pt.)

PRF-12

MRF-12

G - Adaptor

(5/8 - 4/7)

Storm collar

Support ring

MEXT
Solid Section

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Firestop

2' min.

MXT-10

Adaptor

MEXT

Flue

Collar

2' min.

Storm collar

Support ring

Roof flashing

30' max.

* Minimum 1" clearance to all combustibles

Support plate

Firestop

Installation

B. Vertical (Through-The-Roof) Installations

5/8" with option for 4/7"

n

Vertical rise >12' can be reduced

n

Vertical Terminations must be installed:

minimum 2' (two feet) above the highest point where
vent passes through the roof.

minimum 6' (six feet) from a mechanical air inlet

minimum 18" (1 1/2 feet) from a parapet wall.

n

Maximum vent height is 35 feet above fireplace.
Note: Flame characteristics will change if the maximum vent height
is used.

n

Minimum clearances 1" from vent to all combustible materials must
be maintained.

Figure 13.a

Straight, vertical venting using required adaptor.

n

A maximum of two offsets (each offset has two 90° bends) may be
made and shall not exceed total length of 25% of the vertical vent height,
when measured center to center of piping.

Example:

Typical vent installation.
20' vertical vent
2 - 2' offsets required
25% of 20' = 5' max. offset allowed

This venting configuration meets requirements.

Figure 14a.

Vertical venting with 1 offset (1 offset= two 90° bends).

Rigid Section

A

A.Male/Female
B.Female/Female
C.Male Flue Collar

B

C

Figure 13b.

Reducing Vertical Vent from 5/8" to 4/7".

Vent Restrictors

When venting vertically, Vent Restrictors may be added to enhance the
burn characteristics of the fireplace.

35' max

35' max