RP620 Power Vent Indoor Gas Fireplace
Page 27
XG0777 - 122014.1
Installation
Section 7: Venting Configuration for PVHIN58-300 with TMHIN58-40
Minimum 7' of pipe
between fireplace and
power vent
Vent configurations can include vertical sections, horizontal sections, elbows, flex and/or rigid vent
sections. The maximum length of any vent run is 80'. Follow the rules outlined below to determine your
specific vent options. All venting is to be 5" inner and 8" outer sizing. Because this appliance intended to
only be installed with a power vent termination, vertical and horizontal runs can be calculated in the same
manor.
Flexible venting does not flow quite as well as rigid pipe, so a factor needs to be applied, making the total
allowable vent run shorter than rigid pipe.
* Not for rigid elbows used in between flex sections
Venting Calculation
Rigid Vent
Flex Venting
Maximum Vent Run - Rigid
50' total length
40' total length
90 degree elbow
subtract 10' each
* subtract 5' each
45 degree elbows
subtract 5' each
* subtract 2' each
Down sections
subtract 2' for every 1' down
subtract 2' for every 1' down
Flex Venting (if mixed with rigid)
Subtract 1.3' for every 1'
section
Figure 19. Venting Configuration
Vent configurations can include vertical sections, horizontal sections, elbows, flex and/or rigid vent sections. The maximum length of any vent
run is 50'. Follow the rules outlined below to determine your specific vent options. All venting is to be 5" inner and 8" outer sizing. Because
this appliance is intended to only be installed with a power vent termination, vertical and horizontal runs can be calculated in the same manor.
Flexible venting does not flow quite as well as rigid pipe, so a factor needs to be applied, making the total allowable vent run shorter than
rigid pipe.