Section 3-3-3: Heat Shields
Installing a Wall Mounted RHS8 Heat shield

The RHS8 Heat shield CANNOT be used WITHIN 36" horizontal

or 60" vertically of the fireplace, (see figure 14a). For applications

within these dimensions the RHS101 Heat Shield MUST be used.
To install the RHS8, frame an opening in combustible construction,

Figure 14 below. Slide the Heat shield in place over the vent pipe

which attaches to the fireplace. After the fireplace and vent pipe has

been installed, clearances should match the dimensions in Figure 14.

Figure 14. RHS8 Installation. (Install by sliding over vent pipe where it

passes through the combustible construction).

Figure 14a. RHS8 Installation. (Minimum requirements).

Figure 15. RHS101 Installation. (Install by sliding Outer Section over

vent pipe where it passes through the combustible construction.

Figure 15a. Heat Shield. After sliding the outer section in place.

Figure 15b. RHS101 Installation.

Installing a Wall Mounted RHS101 Heat shield.
The RHS101 Heat shield MUST be used where the RHS8

Termination (Figure 14 and 14a) CANNOT be used. Use the

RHS101 where any of the dimensions are within the parameters

shown, figure 14a. To install the RHS101, Slide the Inner Section

over the vent pipe that will connect to the fireplace. Then fasten the

vent pipe to the back of the fireplace with a minimum of three sheet

metal screws. From the outside slide the RHS101 outer section on

see Figure 15. To complete the installation fasten the Heat Shield

Outer Section & Termination frame to the structure Figure 15a.

RHS8 Heat Shield

1” Min. Both sides Typical

1” Min.

1” Min.

Combustible Framing

Termination

Drywall / sheetrock
RHS101 Heat Shield, inner Section

RHS101 Heat Shield

Outer Section

Combustible

framing

Termination

Drywall / sheetrock
RHS101 Heat Shield, inner Section

RHS101 Heat Shield

Outer Section

Vent pipe, from fireplace

Outer Shield 10 1/4”

3/8” Min. Both sides Typical

3/8” Min.

3/8” Min .

Combustible Framing

Inner Shield 9 3/8”

RHS8 Heat

Shield

36” Min

60” Min.

Termination

Note: Images are shown without screens for clarity purposes. How-

ever, your fireplace should not be operated without proper installation

of screens.