Setpoint Parameters
Control Mode
Menu to
Adjust
Setpoint
Setpoint Range
Preset Values
1
2
3
Capacity Setpoint
•
•
•
2
10-100%
100%
Control Humidity Setpoint
•
2
20-98%
35%
Limit Humidity Setpoint
•
•
2
20-99%
75%
High Humidity Alarm
•
2
20-100%
99%
Low Humidity Alarm
•
3
10-98%
10%
Staging
•
•
•
3
1-3
1
Proportional Band
•
3
+/- 2-15%
+/- 10%
Integration Period
•
3
0-60 min
30 min
Throttling Range
•
•
3
0-25%
10%
Unit Address
•
•
•
3
0-99
01
Run Time
•
•
•
5
0-999, 999 hrs
0
Limit Input
•
•
5
Enable/Disable
Enable
Control Input
•
•
•
5
Enable/Disable
Enable