beautypg.com

Herrmidifier Herrmidicool User Manual

Page 3

background image

Herrmidicool IOS Manual

I n s t a l l a t i o n , O p e r a t i o n & S e r v i c e M a n u a l

3

www.herrmidifier-hvac.com

When the humidity requirement has been satisfied, the EST-

1250 will turn off the demand signal to the AH-1109, which

will close the water solenoid, modulating water valve and

the air solenoid. Water pressure is bled instantly to drain via

the drain solenoid. Air pressure is relieved slowly through

the atomizing heads. The air will dry the internal portions

of the head maximizing the maintenance interval. An air-

proving switch (included) ensures there is airflow prior to the

humidifier turning “On.”

Types of Control

The Herrmidicool System is available with three (3) types

of control – (1) On/Off, (2) Proportional, and (3) P+I – these

provide “good,” “better,” and “best” control.

1. On/Off – Humidity is sensed by a humidistat that

provides digital (On/Off) input to the humidifier.

Humidity swings above and below the setpoint based

on tolerance and accuracy of the humidistat. Due to the

limited controllability of an On/Off controlled adiabatic

humidifier, this control scheme would only be used in

very specific applications.

2. Proportional – The variation between the control input

signal and the humidity setpoint results in adjustments to

the unit output. Variations will be smaller than with “On/

Off” control and will be within the control band.

3. Proportional + Integral – The P + I control simply evaluates

the actual humidity vs. desired humidity over a period

of time or integration period. The humidity difference, or

offset, is corrected by an offset correction. This correction

shifts the bandwidth up or down to attempt to eliminate

the offset condition. This type of control is standard with

AH-1200 Series Control Cabinets. Included with these

cabinets are two humidity sensors. One for return or

room sensing, the second for supply or limit sensing.

II. Unit Operation

The Herrmidicool system is an in-duct air/water atomization

system designed to introduce atomized water into the

airstream. The AH-1200 Series includes two sensors and

an air proving switch. From the inputs of these controls, the

EST-1250 microprocessor creates a demand signal that is

forwarded to the AH-1109 atomizer control board.

AH-1200 Series Control Cabinet

Systems provided with the AH-1200 Series Cabinet include

two duct (room sensors optional) sensors and an air proving

switch. One duct sensor, the “control,” monitors the return air

relative humidity. The other duct sensor, the “limit,” monitors

the relative humidity downstream of the humidifier.

The EST-1250 Control Board compares the two sensor

inputs to the corresponding user selected control setpoints. If

both humidity readings are below their respective setpoints,

the controller will select the value closest to its setpoint and

determine an appropriate demand signal based on that.

The demand signal is fed from the EST-1250 controller to the

AH-1109 atomizing control board.

Once it receives a demand signal from the EST-1250

controller, the AH-1109 will energize the air solenoid. A

pressure switch on the air control section will verify sufficient

air pressure, then the water solenoid will be energized and

the modulating water valve will open to the appropriate level

as dictated by the demand signal.

As the demand signal varies up and down, the modulating

water valve will open and close accordingly. The air pressure

will remain constant allowing finer droplets to be produced as

the system modulates down and evaporation becomes more

difficult.

Control Cabinet