beautypg.com

No faults present in system – Herrmidifier Herrmidicool User Manual

Page 10

background image

Herrmidicool IOS Manual

I n s t a l l a t i o n , O p e r a t i o n & S e r v i c e M a n u a l

10

www.herrmidifier-hvac.com

Start-Up

After total installation is complete, the Herrmidicool system

is ready to start. Refer back to the Start-Up Checklist prior to

Start-Up below.

I

MPORTANT: Before scheduling factory start-up, please

have any issues relating to the “Check List” resolved.

If additional trips are required, additional start-up money

will be required!

1. Blow out air and water lines to the control cabinet.

2. Set all controls to their lowest setting (control and limit

if applicable). This allows the system to be turned “on”

without the atomization process being started.

Control Mode:

• Mode 1 (On/Off) – Turn the dial to the Off position or

its lowest setting

• Mode 2 (Proportional) – Set the controller to send the

lowest signal in the range (i.e. 0 VDC in a direct

0-10VDC range).

• Mode 3 (P + I) – Set the “control setpoint” through

Menu 2 at least 11% below the “Control RH” display

in Menu 1.

3. Set the high limit to its highest setting (all control modes).

4. Set Control input to get the Herrmidicool System to

attempt 100% capacity as follows:

• Mode 1 (On/Off) – Turn to full “On” or highest

number possible.

• Mode 2 (Proportional) – set controller to send a

full signal (i.e. 10 VDC in a direct 0-10 VDC output

range).

• Mode 3 (P + I) – Set “Control Setpoint” through Menu

2 20% above “Control RH” as displayed in Menu 1.

5. Once the units get the signal to run and unit is turned

“On,” the air solenoid will energize within 5 seconds. Once

the air pressure switch detects sufficient air pressure, the

water solenoid will open.

6. With individual air and water valves at atomizing heads

closed, blow out the air and water lines through the hose

bibs.

7. A factory-trained technician will complete the balance of

the start-up.

Maintenance

• Air Compressor – follow manufacturer’s recommended

instructions.

• Atomizing Heads – clean dust and debris from outside of

heads as required. If raw water is used, we recommend

removing the atomizing nozzles and strainer screens

once a year for disassembly and cleaning. DO NOT

use a wire or other foreign object to clean nozzle as this

could ruin the orifice.

• Air & Water Lines – blow out once a year. Check joints

for leaks once a year.

• Strainers on air/water control sections should be cleaned

once a year.

• Sensors/transmitters should be checked once per year.

• Solenoid valves should be checked once a year for

proper operation and closure.

Diagnostics

The Herrmidicool humidifier includes built-in diagnostics ca-

pability to identify potential problems, protect the system, and

minimize service/repair time. Should the system detect a criti-

cal condition, a “fault” warning will be displayed on the LCD.

Certain faults prompt immediate system shutdown to protect

the unit or ductwork. Other faults allow the unit to continue to

operate but alert the operator to potential problems that require

maintenance. Other faults, which are designed for initial system

tune-up or preventative maintenance, are classified as “non-in-

dicating.” These faults are viewed by pressing the “fault” key on

the control panel. The table reflects all of the faults the system

is capable of detecting. Please note, however, that certain faults

are unique to certain control modes or networked systems and

are only visible where applicable.

During operation, when an “indicating” fault occurs, the word

FAULT will be visible in the lower right hand section of the LCD.

The red fault light will also be illuminated.

If an “indicating” fault has been detected or a preventative check

is being performed, follow this procedure to determine the cause

of the fault:

1. The LCD must be in the MAIN MENU to access diagnos-

tics. Press “FAULT” key to determine the type of fault.

2. Press the up arrow to determine if there is more than one

fault.

3. If possible, correct the condition causing the fault signal or

plan corrective action.

4. Press “ENTER” to clear the fault signal from the display.

When “ENTER” is pressed, all faults registered in the unit

will be cleared. If the condition causing the fault is not cor-

rected, another fault signal will occur.

5. Under normal operating conditions, pressing the “FAULT”

button will prompt the following display:

NO FAULTS PRESENT
IN SYSTEM