beautypg.com

Herrmidifier Herrmidicool User Manual

Page 12

background image

Herrmidicool IOS Manual

I n s t a l l a t i o n , O p e r a t i o n & S e r v i c e M a n u a l

12

www.herrmidifier-hvac.com

ATOMIZING HEAD ADJUSTMENT

The atomizing heads are factory adjusted and tested. Typically,

no adjustment is required unless the atomizing heads have

been disassembled for maintenance. Do not adjust individual

atomizing heads to reduce capacity or enhance performance.

This is done only by changing the operating pressures for the

entire system.

1. Turn the Herrmidicool System “On” to full output and

check that the air and water pressures are correct.

2. Remove the cap from the back of the atomizing head.

3. Using a screwdriver, slowly turn the spring tension nut

clockwise until the atomizing heads stops spraying.

4. Note the position of the spring tension nut.

5. Back the spring tension nut out two full turns

counterclockwise.

6. If head is not spraying at start of procedure, back out

spring tension nut until head starts to spray and then

begin step 3.

Warning

Absolutely no other components may be mounted inside

or electrically tapped into the humidifier without voiding

the warranty.

AH-1200 SERIES

Troubleshooting with Fault Indication

The following alarm conditions are built into the system.

A. Airflow/High Limit – The microprocessor has detected a

problem with the On/Off air proving circuit connected to

terminals #5 and 15 on terminal strip #1. Check for 20

VDC on terminal strip #5 to ground and #15 to ground.

If air proving switch is closed, you will have 20 VDC

at both terminals. If you have 20 VDC at one of these

terminals, then there is a problem with the air proving

circuit. Investigate and correct problem. If you have this

fault indicated and the voltage check is correct, consult

factory.

B. High Humidity Alarm – Humidity in the space or return

air duct being measured by the control sensor has

exceeded the preset alarm limit. This alarm is only

available on P + I Control Units (Mode 3 – Standard

configuration for AH-1200 Units).

Possible causes of this alarm:

1. Tampering with the control humidity setpoint

2. Alarm setpoint too close to control setpoint

3. Humidifier is powered but not operating and RH

is above setpoint. If system design required this to

happen, you may:

a. Reset your alarm setpoint

b. Turn off humidifier at main disconnect until

humidification season returns.

4. Sensor wiring has failed.

C. Low Humidity Alarm – Humidity in the space or return air

duct being measured by the control sensor has dropped

below the preset alarm level. This alarm is only available

on P + I Control Units (Mode 3 – Standard configuration

for AH-1200 Units).

Possible causes of this alarm:

1. Air handling system limiting output of humidifier as

controlled by limits due to psychrometric conditions.

2. Alarm setpoint too close to control setpoint

3. Humidifier is powered but not operating and RH is

below setpoint. You may:

a. Turn the humidifier “On” to satisfy

b. Adjust the low humidity alarm setpoint.

4. Sensor wiring has failed.

D. Humidity Sensor Failed – This alarm is only available on

P + I Control Units (Mode 3 – Standard configuration for AH-

1200 Units). The sensor has registered a humidity reading

of 100% or more, or 4% or less for more than 5 seconds.

System will operate based on the other sensor until corrective

action is taken. If both sensors fail, the system will shutdown.

Possible causes of this alarm:

1. Failed humidity sensor or wiring.

2. Position of humidity sensor is too close to atomized

spray discharge.