Herrmidicool IOS Manual

I n s t a l l a t i o n , O p e r a t i o n & S e r v i c e M a n u a l

11

www.herrmidifier-hvac.com

System Fault Conditions

(See Troubleshooting Section for corrective action)

Fault

Operation

Status

Comments

Air Flow / High Limit

System

Shutdown,

Automatic

Reset (1)

Insufficient airflow/

high limit setting

exceeded

Hi Humidity Alarm (2)(3)

Continued

Operation

Alarm threshold

achieved

Low Humidity Alarm (2)(3)

Continued

Operation

Alarm threshold

achieved

Humidity Sensor Failed (2) Continued

Operation

unless both fail

Humidity less than

4% or greater than

100%

1. Automatic reset will resume normal operation once the

circuit is closed.

2. Proportional + Integral Control Only

3. Indicating Fault

EXTENDED SHUTDOWN

After an extended shutdown, air and water lines should be

blown out prior to resuming normal operation

Atomizing Head Operation

The Herrmidifier atomizing heads operate with the water

pressure higher than the air pressure. As air enters the

atomizing head, it flows in a centrifugal motion inside the air

nozzle and around the outside of the water nozzle. As the

water enters the atomizing head, it creates pressure against

the diaphragm and compresses the spring located on the

opposite side of the diaphragm. The motion of the diaphragm

pulls the water valve disk away from the bottom of the water

nozzle allowing water to flow through the water nozzle. As

the water exits the water nozzle, it become atomized by the

compresses air inside the air nozzle and exits the atomizing

head as a fine spray.

Pressure Settings

IMPORTANT: The air and water pressures to the atomizing

head should only be adjusted when the humidifier is at full

output. In other words, when the modulating water valve is

100% open the controls are calling for maximum capacity.

Do not attempt to adjust the air and water pressure settings

at any other time. The instructions below assume that the

atomizing heads are installed at the same elevation as the

water control section. Adjustment from this standard must be

made to compensate for any elevation differences between

the water control section and the atomizing head manifold.

1. Set the air pressure at 30 psig.

2. Set the water pressure at 33-38 psig according to the

atomizing head capacity as listed below:

a. 6 lb/hr.

35 psig

b. 8 lb/hr.

38 psig

c. 10 lb/hr.

33 psig

d. 12 lb/hr.

35 psig

e. 15 lb/hr.

37 psig

The water pressure settings listed above will allow the

atomizing heads to perform at their rated capacity (lb/hr.).

It may be desired to deviate slightly (1-2 psig) from the

standard settings in order to enhance performance. Slightly

lower water pressures will result in a finer atomized spray

(smaller droplet size). Be aware that any adjustments such

as this will also reduce the rated capacity of the heads. Use

caution accordingly.