beautypg.com

Herrmidifier Herrmidicool User Manual

Page 6

background image

Herrmidicool IOS Manual

I n s t a l l a t i o n , O p e r a t i o n & S e r v i c e M a n u a l

6

www.herrmidifier-hvac.com

Control Circuit Connections

I. Mode 1--On/Off (OPTIONAL – Limited Application)

1. Control Input - Unit will operate with any two-position

device. Demand for humidity will close the contact.

2. Limit Input - Unit will operate with any two-position

device. The humidistat contact will open on humidity

rise.

II. Mode 2 -- Proportional (Optional – Limited Application)

A. Control Input - Interpreted by the humidifier as a

demand of output signal. Input device should be linear.

Unit can accept any VDC or mADC signal within a

range of 0-20 VDC or mADC.

B. Limit Input - Unit may accept any modulating input

within the same ranges as the control inputs listed

above.

1. Proportional VDC or mADC

2. Resistive

3. Two position device

Additionally, a P + I sensor may be used as a limit input.

1. VDC

2. mADC

III. Mode 3 - Proportional + Integral Configuration

1. Control Input - Unit will accept any sensor input that

provides a VDC or mADC signal within a range of 0-20

VDC or mADC that is proportional to the humidity level

in the air. The sensor may be direct or indirect acting

but must not have impedance greater than 500 ohms,

and should be linear. Example - A direct acting 2 - 10

VDC wall sensor will send a 2 VDC signal if the R.H.

level in the space is 10%; it would send a 10 VDC

signal if the R.H. level is 90%. The humidifier receives

this input and compares it to the setpoint that has

been programmed into the unit. The microprocessor

modulates the output capacity of the atomizer. The

adjustable integration period will review performance

over the given time and will make tuning adjustments

by shifting the proportional bandwidth to correct for

over or under humidification offsets automatically.

2. Limit Input - Unit can accept any two-position device or

any sensor input as specified above.

1. Two position device

2. VDC sensor input.

3. MADC sensor input.

Operating Instructions

Setpoint Parameters

Your AH-1200 Series unit has been preset for 1 of 3

control modes.

1. On/Off

2. Proportional

3. Proportional + Integral (Standard)

With each control mode, there is a specific set of operating

parameters and setpoints that apply. All of the setpoints have

been preset at the factory to simplify the start-up procedure.

The following table identifies the parameters, setpoints and

preset values that apply to each mode.

Standard units have the modulating limit feature enabled. If

for some unique application, an “On/Off” type or no high limit

is used, the “Limit Input” and “Throttling Range” screens will

not be visible or used.

Parameter Definitions: All Control Modes

Output Rating – Unit design capacity (lbs/hr.)

Capacity Setpoint – Output capacity as a % of the output

rating.

Unit Address – In network installation; “master” is “00”,

“slaves” “01” to “99”.

Run Time – Hours of operation

Control Input – Space or Return Air humidity input

device.

Specific Control Modes (See Chart Page 7)

Control Humidity Setpoint – Desired %RH

Limit Humidity Setpoint – Maximum allowable %RH

Low Humidity Alarm – Indication humidity levels beneath

alarm setpoint.

Proportional Band – Humidity span around control

setpoint where modulation occurs.

Integration Period – Length of time period for %RH

evaluation and adjustment

Throttling Range – Humidity range below limit setpoint

where modulation occurs.

Limit Input – Modulating high limit from a controller or

sensor.

High Humidity Alarm – Indication of humidity levels

exceeding alarm setpoint.

All setpoints have preset default values to simplify

programming – Instructions for adjustment are following.