III. Installation

Allowable Operating Conditions

Ambient Temperature: 40°-120°F (4°-50°C)

Ambient Relative Humidity: 0% - 90%

Line Voltage: 120 VAC,15% to +10% Nominal

Frequency: 50/60 Hz

Supply Air Pressure: 60-200 psig

Supply Air Quality: Filter clean and dry to 35°F dew point.

Supply Water Temperature: 40°-100°F (4°-38°C)

Supply Water Pressure: 50-100 psig

Supply Water TDS: less than 50 ppm: Consult Factory

with water analysis and application data prior to selecting

equipment.

NOTE: If units are mounted in outdoor enclosures, conditions

inside enclosure must be maintained as shown above.

Mounting

The Herrmidicool system consists of two basic components:

the control cabinet and the atomizing head manifold

assembly.

The control cabinet should be mounted so that the water

outlet of the control cabinet is level with or below the water

manifold in the air handler. Air vents must be mounted on

any loops necessary to connect the cabinet to the manifolds.

Minimum Cabinet Clearances:

Top: 1’

Bottom: 2’

Sides: 2’

Front: 4’

Hang the cabinet on the wall or unistrut mounting frame.

Two keyhole slots and two additional mounting holes are

provided. Be sure the unit is level and mounted directly to

the wall to wood studs as least 2” thick (or equivalent).

The atomizing head manifolds consisting of air manifolds,

atomizing heads, water manifold and unistrut brackets are to

be located as shown on specific layout drawings with each

job. Typically, a “unistrut” style mounting structure is field

fabricated to support the atomizing manifold.

Manifold Installation:

1. Install the air/water manifolds per the layout drawing for

project.

2. Use only copper, plastic or stainless steel piping as

specified in your print package.

3. Keep runs between control cabinets and heads as short

as possible.

4. Piping runs between control cabinets and manifolds

should be as direct as possible. If loops are unavoidable,

automatic air vents must be supplied and installed.

WARNING

Do not mount any controls inside the unit or tap power

from any location in the unit, except as stated in these

instructions. Do not place objects near the cabinet.

Do not attach to dry wall without studs.

Plumbing

Each cabinet has an air inlet, water inlet, air outlet, water

outlet and a drain outlet. All air connections are ¾” and all

water connections, including drain, are ½”.

NOTES:

1. Drain loop must extend 3” above highest location of

heads or water outlet port on cabinet. This loop allows

water pressure to be relieved on system shutdown. If

blowdown system is used, drain loop is not required.

2. Piping from control cabinet to manifolds should be ¾” for

the air and ½” for the water piping unless otherwise shown

on your job specific drawings provided for your project.

CAUTION

Any minerals that are in the water will be injected into

the airstream. Your application/process may require

some means of air or water filtration to complete a

successful application. Consult the factory if you

should have any questions. Softening the water

only increase the TDS level.

NOTE:

Inlet water pressure must be in range of 50-100 psig. Consult

the factory if you are outside this range.