Groth 3000 Series User Manual
Page 9

6
FLOW CAPACITY SETTING 
 
Unless otherwise specified, the orifice selector sleeve 
[34] is factory set at the 100% full open position. If 
reduced capacity is specified on an order, the sleeve 
is set at the appropriate restriction. Actual capacity at 
any other position can be calculated by multiplying 
the capacity value from Table 2 for a specific 
pressure by the decimal fraction from Table 6. 
 
Flow capacity can be adjusted by rotating the orifice 
sleeve (See Warning). It has a series of indexing 
holes, four of which are marked with the numbers 1-
2-3-4 (See Figure 5). Two unmarked holes are used 
to assist when rotating the sleeve. Adjustment can be 
made by loosening and backing the lockdown screw 
completely out of the body. The sleeve position can 
then be viewed and the sleeve rotated by inserting a 
small diameter wire into the holes. 
 
Figure 5: Orifice Sleeve Orientation
 
 
 
 
2
3
2
34
36
35
 
 
 
 
 
 
When replacing the locking screw, grease the O-Ring 
[35] and slip it over the screw threads. Thread the 
screw [36] into the body, finger tight, until the point 
enters the sleeve and the head seats onto the O-Ring. 
Then wrench tighten the head firmly against the 
body, compressing the O-Ring. 
 
Sleeve position and valve capacity are shown in 
Tables 2 and 6. These tables are based on the supply 
pressure at the regulator inlet and piping as 
recommended in the installation section. 
 
 
 
 
 
 
 
TABLE 6
ORIFICE CAPACITY
Orifice Sleeve
Position
Flow
Multiplier
1
1.0
2
0.75
3
0.50
4
0.25
 
 
 
 
 
 
WARNING
The adjustable orifice is located in a pressure 
containing chamber. Close the supply valve and 
release all pressure before making adjustments. 
WARNING
The regulator orifice sleeve is factory set at the 
specified flow capacity. When repairing a 
regulator, note the position of the indexing holes at 
disassembly. The sleeve must be re-assembled in 
the same position to ensure the proper flow 
capacity. NEVER adjust the orifice sleeve position 
without written instructions from your plant 
operations group. 
