beautypg.com

Troubleshooting guide – Greenheck Vari-Flow Air Management Systems (472966) User Manual

Page 15

background image

15

Vari-Flow Air Management System

®

Troubleshooting Guide

Issue

Possible Cause

Recommended Solution

Smoke spilling out of hood
at 100% operation

Max fan speed has been
scaled down from 100%

Increase exhaust fan maximum speed to 100%.

Improper hood design

Check hood overhang, cross drafts, or proper
make up air

Smoke spilling out when
hood running at lowest
speed

Fan minimum speed set
too low

Increase exhaust fan minimum speeds

Improper hood design

Check hood overhang, cross drafts and proper
make up air

Fans do not turn up to
maximum speed

Dirty temperature sensor

Clean grease from temperature sensor

High temperature set
too high

Decrease the high temperature set point
(115°F default)

Fans do not turn down to
minimum speed

Dirty temperature sensor

Clean grease from temperature sensor

Low temperature set
too low

Increase the low temperature set point
(90°F default)

Exhaust fan on and supply
fan off

Broken supply fan belt

Replace fan belt

Fire mode

Check fire contact connection

Fans rotate in wrong
direction

VFD output wiring incorrect

Switch any two leads on the hood side of the
VFD to the fan motor

100% override does not
increase exhaust

Exhaust already at 100%

Proper Operation

Bad wiring connection

If fan 100% LED does not light check keypad
connection

Fan switch is on, but fans do
not turn on

Broken fan belt

Replace fan belt

VFD fault

Check VFD for faults

Bad wiring connection

If fan on/off LED does not light check keypad
connection

Hood lights LED on, but no
lights come on

Light bulbs are burned out

Replace hood light bulbs

Bad wiring connection

If hood lights LED is lit check wiring connection to
hood lights

Fan 100% LED is flashing

Vari-Flow is operating
in temperature interlock
mode

Press the Fan On button to manually turn on the
fans

Fans do not turn on
automatically

Temperature Interlock
Enabled set to no

Turn the Temperature Interlock Enabled to yes

Interlock set point too high

Adjust the temperature interlock set point
(90°F default)

Pressure Sensor Fault

Kinked hose

Remove kink or replace hose

Controlled space not
holding pressure

Adjust the static pressure set point

Fire

Fire system microswitch is
in the fire position

Check the fire suppression microswitch
connections

Temperature Sensor Fault

Dirty/burned sensor

Clean/replace sensor

Incorrect programming

Check the temperature sensor settings

Exhaust VFD Fault

VFD over current

Check fan rotation

Fan FLA not set in the VFD
parameters

Check the VFD overload settings (PAR E2-01)

Supply VFD Fault

VFD over current

Check fan rotation

Fan FLA not set in the VFD
parameters

Check the VFD overload settings (PAR E2-01)