Sequence of operation – vari-flow, Fire mode operation, Fault & failure operation – Greenheck Vari-Flow Air Management Systems (472966) User Manual

Page 13: Vari-flow air management system

background image

13

Vari-Flow Air Management System

®

NO

TRAK

PRES

YES

Exhaust off

in Fire

Exhaust on in Fire

OFF

ON

NO

YES

NO

YES

Hood Switch

Temperature

Interlock

Fan(s) will run

START FAN

FIRE MODE OPERATION

SEQUENCE OF OPERATION – VARI-FLOW

FIRE?

Exhaust

Fan(s)

remain ON

Supply Fan(s)

will turn OFF

System Start Stop

NO

YES

Fan(s) will run

START FAN

FIRE?

Exhaust

Fan(s) will

turn OFF

Supply

Fan(s) will

turn OFF

MUA/SF VFD

Interlock

Start & Run

Hood VFD

DDC

Temperature

Control

Enabled

Compare Highest

Temperature

Readings with Hood

Operating Temp

Setpoint

Hood VFD Speed

Set According to

Temperature

Hood Full Speed

DDC

Temperature

Control

Enabled

Hood VFD Set to

Full Speed

15 minute timer /

Full Speed Cancel

Full Speed

Cancel

Return to System

Start/Stop

MUA/SF/OA Damper Pressure Control

Compare Space Static

Pressure Reading

with Space

Pressure Setpoint

(+.05”WC, adjustable)

MUA/SF

VFD Speed Set

According to

Pressure

OA Damper

Position Set

(open/closed)

Hood Running

Signal Received

Temp

Sensor

Failure

Exhaust VFD

Fault

System Failure

Light On

DDC

Temperature

Control

Enabled

Hood VFD Set to

Full Speed

Space Pressure

Sensor Failure

(Beyond -

.25/+.25”WC)

MUA/SF

VFD Fault

Hood VFD Set to

Full Speed

System Failure

Light On

FAULT & FAILURE OPERATION

Pressure or

Tracking?

MUA/SF VFD Speed

Set by Proportional

Tracking

Set MUA to run

on Tracking