Vari-Flow Air Management System

®

Exhaust -

continued

EF Max Fan Speed Descriptors/Value Default Use

EF1 Max

0-100%

100%

Indicates the maximum fan speed to meet design
airflow requirements for EF1

EF2 Max

0-100%

100%

Indicates the maximum fan speed to meet design
airflow requirements for EF2

EF3 Max

0-100%

100%

Indicates the maximum fan speed to meet design
airflow requirements for EF3

EF4 Max

0-100%

100%

Indicates the maximum fan speed to meet design
airflow requirements for EF4

EF5 Max

0-100%

100%

Indicates the maximum fan speed to meet design
airflow requirements for EF5

Exhaust Temperature Set Points*

EF1 Low Temp

°F

90°F

The temperature at which EF1 runs at the minimum speed.

EF1 High Temp

°F

115°F

The temperature at which EF1 runs at the maximum speed.

EF2 Low Temp

°F

90°F

The temperature at which EF2 runs at the minimum speed.

EF2 High Temp

°F

115°F

The temperature at which EF2 runs at the maximum speed.

EF3 Low Temp

°F

90°F

The temperature at which EF3 runs at the minimum speed.

EF3 High Temp

°F

115°F

The temperature at which EF3 runs at the maximum speed.

EF4 Low Temp

°F

90°F

The temperature at which EF4 runs at the minimum speed.

EF4 High Temp

°F

115°F

The temperature at which EF4 runs at the maximum speed.

EF5 Low Temp

°F

90°F

The temperature at which EF5 runs at the minimum speed.

EF5 High Temp

°F

115°F

The temperature at which EF5 runs at the maximum speed.

Exhaust Mode

Exhaust in Fire

No / Yes

Yes

Indicates the exhaust fan(s) will run in case of fire

Fans Full Speed

No / Yes

-

Indicates the operator overrode the exhaust fan to full
speed operation

100% Timer

Minutes

15 min

The set time the fan 100% override runs for.

Time Left

Minutes

-

Indicates the time remaining for the full speed
override

Exhaust Fans*

Fan1 Connected

No / Yes

Yes

Indicates if EF1 is connected

Fan2 Connected

No / Yes

No

Indicates if EF2 is connected

Fan3 Connected

No / Yes

No

Indicates if EF3 is connected

Fan4 Connected

No / Yes

No

Indicates if EF4 is connected

Fan5 Connected

No / Yes

No

Indicates if EF5 is connected

Grease Grabber H2O with Vari-Flow Settings

GGH2O/
Vari-Flow Settings

Descriptors/Value Default Use

GGH2O Force Fan Off No / Yes

No

If yes the exhaust fan(s) are forced off to prevent
water from being drawn into the exhaust duct during
the wash cycle. The fan button on the keypad is
disabled.

GGH2O Fan Dry
Active

No / Yes

No

If yes, the exhaust fan(s) is(are) forced on to dry the
filters following the wash cycle.

GGH2O Fan Mode

0-10 VDC

-

0 V-Fan(s) Auto

0-10 VDC

-

5 V-Fan(s) Off

0-10 VDC

-

10 V-Fan(s) Dry

* To see values, you need to log in.