7

Network Interface Controller for Tempered Air Products

E.

Board Switch

The Board Switch menu allows the user to jump between different controllers
with a remote display. This requires a remote display, along with additional
controllers, set-up in a pLAN network. A pLAN can consist of up to 32 devices, in
different combinations, but a maximum of 31 controllers.

w

hen

vIewIng

thIs

screen

from

a

remote

DIsplay

,

the

user

Is

aBle

to

change

whIch

controller

s

menu

shoulD

Be

DIsplayeD

.

Unit Address: The pLAN address of the controller the display is currently
accessing.
Switch to unit: The pLAN address of the controller the display would like to
access.

Board Switch

Unit Address:

1

Switch to unit:

1

1 . . . . . . . . . . 16

17 . . . . . . . . . 32

The Overrides menu is for start-up, commissioning and troubleshooting.
This menu allows the user to override the control loops. If further control is
required, the user can also manually control the controller inputs and outputs.
To access the Overrides sub-menu, enter the service password (Default=1000).

To manually override an output, in each respective screen, change the override
from No to Yes, then change the Position to open or closed or adjust the vdc
output setting.
To resume normal operation after overriding the controller, simply cycle power
to the unit.
This menu allows the user to manually control the outputs of the controller. The
user can manually control the analog outputs and digital outputs. EXTREME
CAUTION should be used when manually controlling the outputs and should
only be used as a troubleshooting feature. If the controller is powered down,
overrides are reset to off. Therefore, if using this troubleshooting feature, the
best way to clear manually input values is to power down the controller.

F.

Service

e

nterIng

the

I

nformatIon

suB

-

menu

wIll

DIsplay

InformatIon

aBout

the

controller

anD

the

program

loaDeD

on

the

controller

.

Code: Controller setup code determines functionality of program. When
contacting the factory, please reference this code.
Manual: Reference this Installation and Operation Manual, available at
www.greenheck.com

The Service menu allows the user to access several sub-menus regarding
controller information, controller overrides, operating hours, BMS configuration,
I/O manual management and Probe Adjustment. The user can also change the
default Service Password (Default=1000) by accessing the Service Settings
sub-menu. By accessing the BMS Config sub-menu, the user can adjust BMS
protocol settings (BACnet, LonWorks, Modbus).

Information

Greenheck Fan Corp.

Code:GXXXXX00XX100b

Ver.: 1.00

05/24/11

Manual: 475262

Bios:

5.12 11/17/10

Boot:

4.07 12/18/11

Testing Overrides

To resume normal operation,

cycle unit power.

F.

Service

a. Information

F.

Service

b. Overrides

t

hIs

screen

allows

the

user

to

overrIDe

the

DIgItal

outputs

.

This screen only appears if the unit is equipped with a digital output option.

t

hIs

screen

allows

the

user

to

overrIDe

the

analog

outputs

.

This screen only appears if the unit is equipped with an analog output option.

Testing Overrides

Override: No Position

NO1-

NO2-

NO3- Unit On/Off: Open

NO4-

NO5-

NO6-

Testing Overrides

Override: No Position

Y2- VFD Supply: 10.0vdc

Y3-

Y4-

®