beautypg.com

G. manufacturer – Greenheck Network Interface Controller (475262 IOM) (Pre May 2013) User Manual

Page 10

background image

10

Network Interface Controller for Tempered Air Products

t

hIs

screen

allows

the

user

to

save

anD

restore

the

Default

parameters

storeD

In

memory

.

If the user would like to save their settings, move the cursor to the SAVE
position and change to YES. This will save all of the current parameters into
memory as Service Settings. If the user would like to restore to these values
at some point in the future, moving the cursor to the RESTORE position, and
selecting YES will restore the controller to the user saved defaults.

User Default Settings

Save? No
Restore? No

G.

Manufacturer

a. Configuration

Configuration menu allows the user to change the setup code for the unit, enable
Scheduling, Holidays, expansion I/O and change Field Card settings. Users are
welcomed to enable Scheduling and Holidays. However, code changes and
expansion I/O enabling are to be done under factory advice only!

t

hIs

screen

DIsplays

anD

allows

aDjustment

of

the

u

nIt

c

oDe

.

This code is set from the factory to operate the components selected with
the unit. When troubleshooting, refer to the wiring diagram sent with the unit
(located on the control center door) to verify the Unit Code is correct. The code
will be listed on the wiring diagram.

t

hIs

screen

allows

the

user

to

enaBle

aDDItIonal

I/o

poInts

.

Unit I/O expansion requires the installation of a pCOe and Field Card. Please
contact the factory for more information.
Enabling the I/O expansion allows the user to add the following points for
monitoring:
• Four analog inputs (0/1vdc, 0/5vdc, 0/20mA, 4/20mA, NTC Temp)
• One analog output (0/10vdc)
• Four digital inputs
• Four digital outputs
The additional I/O points available on the pCOe expansion module allow the
user to monitor and control the additional points over the BMS and user display.

t

hIs

screen

allows

the

user

to

vIew

anD

change

the

controller

p

lan

aDDress

.

A pLAN (pCO Local Area Network) is a Carel proprietary local area network,
allowing the user to connect multiple controllers to one remote display panel.
Each controller on a pLAN must have a unique address.
This address is only applicable for units connected on a pLAN. For BACnet,
LonWorks or Modbus parameters, go to Service > BMS Config.

t

hIs

screen

allows

the

user

to

alter

the

fIelD carD m

oDBus

settIngs

.

The FIELD CARD is used for peripheral device control (pCOe Expansion
Module).
The Modbus settings should only be changed with factory guidance.

Unit Code

Select DDC configuration

code here.
Code: GXXXXX00XX100b

Configuration

Modbus settings
Baudrate: 19200

Stop bit:

2

Parity mode:

None

Timeout: 300ms

Unit Expansion I/O

Enable Expansion:

No

Controller pLAN Setup

Current pLAN Addr:

1

New pLAN Addr:

1

®