Typical wiring diagram – Greenheck Network Interface Controller (475262 IOM) (Pre May 2013) User Manual

Page 14

background image

14

Network Interface Controller for Tempered Air Products

CAUTION

UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.

POWER MUST BE OFF WHILE SERVICING.

NOTES

USE COPPER CONDUTORS ONLY

60° C FOR TERMINALS RATED LESS THAN 100 AMPS.

75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD

NOT EXCEED 0.75 OHM.
FIELD WIRED

FACTORY SUPPLIED AND WIRED

LEGEND

GEXXXXD000XX101BL00

WIRE COLOR CODE

Wiring Diagram Code:

BK

BLACK

BL

BLUE

BR

BROWN

GY

GRAY

LT BL LIGHT BLUE

O

ORANGE

PK

PINK

PR

PURPLE

R

RED

W

WHITE

Y

YELLOW

Wiring Template: L00

GND

Y4

GND

ID2

J13

B5

B6

ID1

B2

B3

B4

J2

B1

GND

CONTROLLER

pCO5 INTERFACE

J12

NO4

NO3

J1

C3

BLUE

G

GO

J3

NO6

NO5

C5

GND

Y1

Y2

J9

Y3

OAI

OAD

NO2

C2

J11

NC1

NO1

C1

(PWM)

J10

DDC Code: Verison - BMS 1.00

TO TERMINAL "R"

R

(0/10V)

(0/10V)

(0/10V)

UNIT ELECTRICAL BOARD TERMINALS/COMPONENTS

NETWORK INTERFACE CONTROLLER/COMPONENTS

NETWORK INTERFACE CONTROLLER TO UNIT CONNECTION WIRING DIAGRAM

G

PINK

TO TERMINAL "G"

G

1

REPLACES S1 FAN SWITCH

FACTORY WIRED

UNIT START/STOP

XXXX 00 0 X X 0 b

ACC

AFTER COOLING COIL TEMPERATURE

EAW

EXHAUST AIR AFTER WHEEL TEMPERATURE

OAAW OUTDOOR AIR AFTER WHEEL TEMPERATURE

OAD

OUTDOOR AIR DISCHARGE TEMPERATURE

OAI

OUTDOOR AIR INLET TEMPERATURE

RAI

RETURN AIR INTLET TEMPERATURE

R20

ROTATION INTERFACE RELAY

TO TERMINAL "C"

C

WHITE

24 VAC

®

TO "13" ON ST1

13

ST1

TO "14" ON ST1

14

FAN PROVING STATUS

TO "NO" ON PS2

TO "C" ON PS2

NO

PS2

C

D

REPLACES FIELD INTERFACE

CONNECTION TO PS2

DIRTY FILTER STATUS

FACTORY WIRED

TO TERMINAL "W1"

W1

1

REPLACES S4 CALL FOR HEAT SWITCH

FACTORY WIRED

HEATING STAGE 1

Typical Wiring Diagram

®