Points list • lonworks – Greenheck Network Interface Controller (475262 IOM) (Pre May 2013) User Manual
Page 12

12
Network Interface Controller for Tempered Air Products
Points List • LonWorks®
Type
NV_Index
Name NV
Type NV
Read (Unit to BMS)
Write (BMS to Unit)
Description
Analog
20
nvoOutsideTemp
105
Read
Outdoor Air Temp (###.#°F)
Analog
21
nvoSupplyAirTemp
105
Read
Supply Air Temp (###.#°F)
Analog
22
nvoColdCoilDisch
105
Read
Cold Coil Temp (###.#°F)
Analog
23
nvoReturnTemp
105
Read
Return AirTemp (###.#°F)
Analog
24
nvoExhDishTemp
105
Read
Exhaust Discharge Temp (###.#°F)
Analog
25
nvoOAAWTemp
105
Read
Outdoor Air After Wheel Temp (###.#°F)
Analog
3
nviHeatOutput
81
Write
Heater output (0-100%)
Analog
4
nviCoolOutput
81
Write
Cooling output (0-100%)
Analog
5
nviVFDSupply
81
Write
VFD Supply Fan Output (0-100%)
Analog
6
nviVFDExhaust
81
Write
VFD Exhaust Fan Output (0-100%)
Analog
7
nviVFDWheel
81
Write
VFD Wheel Output (0-100%)
Analog
8
nviRADamperOut
81
Write
RA Damper Output (0-100%)
Analog
26
nvoVFDSupSignal
44
Read
Supply VFD Monitor Signal (Vdc)
Analog
27
nvoVFDExhSignal
44
Read
Exhaust VFD Monitor Signal (Vdc)
Analog
28
nvoB1User
9
Read
User Define B1 Analog Input
Analog
29
nvoB2User
9
Read
User Define B2 Analog Input
Analog
9
nviY4UserOut
81
Write
User Define Y4 Analog Output
Integer
30
nvoCO2Output
29
Read
CO2 Levels (ppm)
Digital
10
nviUnitOnOff
95
Write
Unit start/stop command
Digital
11
nviResetAlarms
95
Write
Reset alarms command
Digital
12
nviStg1Cooling
95
Write
Cooling Stage 1 Command
Digital
13
nviStg2Cooling
95
Write
Cooling Stage 2 Command
Digital
14
nviStg1Heat
95
Write
Heating Stage 1 Command
Digital
15
nviOccUnocc
95
Write
Occupied/unoccupied Command
Digital
16
nviRemoteExhFan
95
Write
Remote Exhaust Fan Command
Digital
17
nviHGRH
95
Write
Hot Gas Reheat Command
Digital
31
nvoGlobalAlarm
95
Read
Global alarm indication (active when there is at least one alarm)
Digital
32
nvoFanStatus
95
Read
Fan Proving status
Digital
33
nvoFilterStatus
95
Read
Dirty filter status
Digital
34
nvoWheelStatus
95
Read
Wheel status-Not Ok=Wheel not running when commanded on
Digital
35
nvoSupplyTempAlm
95
Read
Supply air temperature low limit alarm
Digital
36
nvoB1Alarm
95
Read
Sensor B1 out of range
Digital
37
nvoB2Alarm
95
Read
Sensor B2 out of range
Digital
38
nvoB3Alarm
95
Read
Sensor B3 out of range
Digital
39
nvoB4Alarm
95
Read
Sensor B4 out of range
Digital
40
nvoB5Alarm
95
Read
Sensor B5 out of range
Digital
41
nvoB6Alarm
95
Read
Sensor B6 out of range
Digital
42
nviB5UserDI
95
Read
User Define B5 Digital Input
Digital
43
nviB6UserDI
95
Read
User Define B6 Digital Input
Digital
18
nviNO1UserDO
95
Write
User Define NO1 Digital Output
Digital
19
nviNO2UserDO
95
Write
User Define NO2 Digital Output
Digital
44
nvoID2UserDI
95
Read
User Define ID2 Digital Input
®