beautypg.com

Troubleshooting ntc temperature sensor chart, Esc and, Enter at the same time, while pressing – Greenheck Network Interface Controller (475262 IOM) (Pre May 2013) User Manual

Page 15: Down or, Alarm, Prg, and, Esc at the same time, while pressing, Down, Up and

background image

15

Network Interface Controller for Tempered Air Products

Display is hard to read.

Unit Controller Display: Hold

Prg

Esc

or

!

ESC and

Prg

Esc

ENTER at the same time,

while pressing

Prg

Esc

DOWN or

Prg

Esc

UP to adjust display contrast.

Remote Display: Hold

Prg

Esc

or

!

ALARM,

Prg

Esc

or

!

PRG, and

Prg

Esc

or

!

ESC at the

same time, while pressing

Prg

Esc

DOWN or

Prg

Esc

UP to adjust display contrast.

Remote display panel
displays “NO LINK” or
is blank.

Hold

Prg

Esc

DOWN,

Prg

Esc

UP and

Prg

Esc

ENTER for 4 seconds. Set the display address

to 32. The display requires a standard 24 AWG six conductor phone cable
connected to the unit controller.

Red alarm button is
flashing.

Press the

Prg

Esc

or

!

ALARM button to review and clear unit alarms. Enter the

DATA LOGGER menu to view previous alarms.

Controller resets itself
or is not on.

Check the supply voltage to the controller at terminals G-G0. The board requires
24VAC. Check the 24VAC transformer in the unit control center.

Menus are locked with
a password.

The factory default Manufacturer Password = 1000.
The factory default Service Password = 1000.

Temperature sensor
failure.

Check the analog input terminal block (labeled terminals B1, B2, B3, etc) for loose
wires. Disconnect temperature sensors to check sensor resistance.

Troubleshooting

NTC Temperature Sensor Chart

120

110

100

90

80

70

60

50

40

30

20

10

0

4 6 8 10 12 14 16 18 20 22 24 26 28

Temperatur

e (

ºF)

Resistance (kΩ)

®