Installation - roof mounted unit arrangement dbc, Step 1 install curb/equipment support(s), Step 2 install combination extension – Greenheck DG / DGX with Pilot Ignition (463555 IOM) (Pre-2008) User Manual
Page 5: Step 4 apply sealant, Step 3 install ductwork
Supply Duct with Duct
Adapter Installed
Exhaust Duct Installed
Sealant
Supply
Ductwork
by Others
Exhaust
Ductwork
by Others
Metal Cover
Equipment
Support
Roof Curb
Exhaust
Supply
1 inch Inside
Flange
Step 1 Install Curb/Equipment
Support(s)
Position curb/equipment support(s) on the roof
(reference the CAPS submittal for placement of
curb/equipment support(s) in relation to the unit).
Verify that all unit supports are level, shim if
necessary. Attach curb to roof and flash into place.
Attach the equipment support(s) to the roof, remove
metal cover, flash to wooden nailer and reinstall
cover.
Step 2 Install Combination Extension
Install combination extension over curb. Lag into
place using wood screws. Locate the extension so
the tall vented side is over the exhaust opening.
Installation - Roof Mounted Unit Arrangement DBC
Installation
Step 4 Apply Sealant
Apply an appropriate sealant around the perimeter of
the curb and duct adapter(s) to isolate fan vibration
and prevent water penetration.
5
NOTE!
The use of a duct adapter is recommended on a
downblast (DBC) arrangement to align the
ductwork with the supply unit. The duct adapter
is only a guide and is not to be used as support
for the ductwork.
Step 3 Install Ductwork
Good duct practices should be followed for all
ductwork. All ductwork should be installed in
accordance with SMACNA and AMCA guidelines,
NFPA 96 and any local codes. Reference the CAPS
submittal for ductwork size and location.
Curb and Equipment Support
Combination Extension
Ductwork
Sealing Ductwork