Start-Up - Blower
Start-Up
Voltage, Hertz,
and Phase
Step 1 Check the Voltage
Before starting the unit, compare the supplied voltage, hertz, and phase with the unit and motor’s nameplate
information.
Step 2 Check the Blower Rotation
Open the blower access door and run the blower momentarily to determine the rotation. Arrows are placed on
the blower scroll to indicate the proper direction or reference the example below.
IMPORTANT!
If the blower is rotating in
the wrong direction, the
unit will move some air,
but will not perform as
designed. Be sure to
perform a visual inspection
to guarantee the correct
blower rotation.
Blower
Rotation
Housing
SPECIAL EQUIPMENT REQUIRED
Below is a list of special tools that are required. A recommended model is shown, but equivalent
products may be used.
Description
Manufacturer-Model
Phone
Website
Voltage Meter
Fluke-179
1-800-44-FLUKE
www.fluke.com
Amperage Meter
Fluke-179
1-800-44-FLUKE
www.fluke.com
Thermometer
Fluke-50
1-800-44-FLUKE
www.fluke.com
Micro Amp Meter
Fluke-16
1-800-44-FLUKE
www.fluke.com
U-Tube manometer
Dwyer-Slack Tube
1-219-897-8000
www.dwyer-inst.com
Tachometer
Monarch-Pocket Tach 100
1-800-999-3390
www.monarchinstruments.com
WARNING!
Disconnect and lock-out all power and gas before
performing any maintenance or service to the
unit. Failure to due so could result in serious
injury or death and damage to equipment.
Pre Start-Up Check
Rotate the fan wheel by hand and make sure no parts
are rubbing. Check the V-belt drive for proper
alignment and tension (a guide for proper belt tension
and alignment is provided in the belt maintenance
section). Check fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness.
NOTE!
To reverse the rotation on three phase
units, disconnect and lock-out the power,
then interchange any two power leads.
NOTE!
To reverse the rotation on single phase
units, disconnect and lock-out the power,
then rewire the motor per the
manufacturer’s instructions.
REFER TO THE START-UP CHECKLIST IN THE REFERENCE SECTION
BEFORE PROCEEDING FURTHER!
Blower Rotation
WARNING!
Check the housing, blower, and ductwork for any foreign objects before running the blower.
Electrical Nameplate
SUP HP
MCA
EXH HP
MOP
VOLTS
HZ
PH