Pump Configuration
SiteOmat Software Set Up
5
In the Specific section, verify the following is set up for the installed pumps
).
• Pulser Type - Select Half Cycle Count Pulse from the drop-down list.
• Pulse Factor - Enter the correct setting for the installed pumps (as 10 or 100).
- 10 - 10:1 Pulser on PUMP
- 100 - 100:1 Pulser on PUMP
• Virtual In Use - Select Enable when a handle switch is not available and select Disable at
all other times.
- This is always required for hose reels for oil and lubricants.
- This is required for some dispensers (PMC Pumps) without proper handle-switch wires.
• Flow Protection timeout - Set this to 70 seconds.
Note: Flow protection timeout controls the active time (70 seconds) of the Virtual In Use
after pulses stop.
6
Repeat steps
(on
for all pumps and oil reels.
7
To save the pump configuration settings, click Save, the Setup screen appears.