MDE-5067 FedEx Islander PLUS FMS Installation Manual · March 2013
Page 3-11
Installing FedEx Islander PLUS FMS
Figure 3-9: Mechanical Pump without Solenoid Valve
Disconnect from motor feed and cap wire.
Islander IN_Use_1A and Line (TB-25 and
TB-41)
Islander Load 1 (TB-49)
Pump Control Maximum Current
Pedestal with up to 4-hose mechanical pumps:
Motor Max: 1 HP @ 115 VAC
~OR~
2 HP @ 230 VAC
Additional relay must be used if pump motor
exceeds these limitations.
Pedestal with up to 8-hose mechanical pumps:
Motor Max: 3/4 HP @ 115 VAC
~OR~
1.5 HP @ 230 VAC
Additional external relay must be used if pump
motor exceeds these limitations.
Neutral to IN_Use 1B (TB-33)