GAI-Tronics 12584-002 I/O Control Module User Manual
Page 4
Pub. 42004-388B
Model 12584-002 I/O Control Module
Page: 4 of 15
\\s_eng\gtcproddocs\standard ioms - current release\42004 instr. manuals\42004-388b.doc
04/07
The DIP switch S4 positions 4-8 set the operating parameters as follows:
Table 2. DIP Switch S4 Positions 4–8: Operating Parameters
DIP Switch
Position
Function
Settings
S4-4
None - not used
N/A
S4-5
None - not used
N/A
S4-6
Automatic input
response
Closed - will wait for a poll request from master controlling
device before sending an input activation data message.
Open - will automatically send a data message when an active
input is detected. The controller will NOT wait for poll request
from the master controlling device.
S4-7 Address
return
Closed - will NOT return the controller’s address (set by hex
switch S1 and S2) when sending a data message to the master
controlling device.
Open - will return the controller’s address (set by hex switch S1
and S2) when sending a data message to the master controlling
device.
S4-8
Data fault
indication
Closed - if data communication is lost with the master controlling
device, all outputs will remain in their current state until data
communication is restored.
Open - if data communication is lost with the master controlling
device, all outputs will flash on/off.