FSR SPC-15 User Manual
Page 4

POWER PRODUCT GROUP
Phone: 973-785-4347 Fax: 973-785-3318
W
eb: www
.fsrinc.com E-Mail: [email protected]
FSR
SPC-15 FRONT
P
ANEL
SYSTEM POWER SWITCH
AND LED:
when the system LED is of
f, pressing the system switch will start the turn-on procedure, and the LED
will illuminate.
When the system LED is on, pressing the system switch will start the turn-of
f procedure, and the LED will tur
n of
f.
This LED blinks
on power up and power down until the cycle is complete.
UNSWITCHED OUTLET
: this outlet is active at all times the equipment is plugged in.
TRIP
LAMP:
a ground closure on the remote trip input (rear panel remote control strip) will sequence the system down and latch on the tri
p lamp.
After the remote trip input is cleared, the trip lamp can be reset by pressing the momentary system power switch.
SYSTEM F
AUL
T
LAMP:
this supervisory indicator will illuminate to indicate that an enabled
AC circuit is not receiving
AC power (faulty output
circuit), or that a disabled
AC circuit continues to receive power (incorrect system wiring, shorted output circuit, etc.).
A
system fault indication will
be provided when a fault indication is detected in the SPC-15 or any expansion stages.
LOCAL
F
AUL
T
LAMP
: this supervisory indicator will illuminate to indicate that a fault has occurred at this local unit.
A
local fault on any un
it in
the system will also activate the system fault lamp.
SURGE CIRCUITS OPERA
TIONAL:
provides supervisory indication that the sur
ge suppression cicuitry is fully functional.