beautypg.com

FSR SPC-15 User Manual

Page 4

background image

POWER PRODUCT GROUP

Phone: 973-785-4347 Fax: 973-785-3318

W

eb: www

.fsrinc.com E-Mail: [email protected]

FSR

SPC-15 FRONT

P

ANEL

SYSTEM POWER SWITCH

AND LED:

when the system LED is of

f, pressing the system switch will start the turn-on procedure, and the LED

will illuminate.

When the system LED is on, pressing the system switch will start the turn-of

f procedure, and the LED will tur

n of

f.

This LED blinks

on power up and power down until the cycle is complete.

UNSWITCHED OUTLET

: this outlet is active at all times the equipment is plugged in.

TRIP

LAMP:

a ground closure on the remote trip input (rear panel remote control strip) will sequence the system down and latch on the tri

p lamp.

After the remote trip input is cleared, the trip lamp can be reset by pressing the momentary system power switch.

SYSTEM F

AUL

T

LAMP:

this supervisory indicator will illuminate to indicate that an enabled

AC circuit is not receiving

AC power (faulty output

circuit), or that a disabled

AC circuit continues to receive power (incorrect system wiring, shorted output circuit, etc.).

A

system fault indication will

be provided when a fault indication is detected in the SPC-15 or any expansion stages.

LOCAL

F

AUL

T

LAMP

: this supervisory indicator will illuminate to indicate that a fault has occurred at this local unit.

A

local fault on any un

it in

the system will also activate the system fault lamp.

SURGE CIRCUITS OPERA

TIONAL:

provides supervisory indication that the sur

ge suppression cicuitry is fully functional.

This manual is related to the following products: