FSR IT-R4S User Manual

Page 8

background image

8

“RS”

Where:
“RS”

Relay

Status

Request.



Relay Response:

The Relay status response will display only what was requested and the configuration

dipswitch 4 status.
“RS”

Ver

Relay Status

Serial 2 baud

Where:
“RS”

Relay

Status

Response.

Ver

Version

Number

Relay Status

relays current status


Serial2 Baud “1” = 2400
“2”

=

4800

“3”

=

9600

“4”

=

19200

“5”

=

38400

“6”

=

57600

(MAS-6200)


The user sends “RS the IT-R4S would respond with “RS R1=O R2=C R3=P R4=O
SB=5”. This response means that relay1 is Open(off), relay2 is on Closed(on), relay3 is
currently being (P)ulsed, relay 4 is Open (off), and Serial 2 baud rate is 38400.

Serial 2-Baud Rate Request:

It may be necessary to change the baud rate on the last pass-through device serial port.

This may happen if the last device doesn’t have the baud rate at 38400, and doesn’t have a
method to change it.

“RB”

Port

Baud rate number

Where:
“B”

Change

baud

rate

request

Port

Serial port number (“2” for IT-R4S)

Baud rate number

Which baud rate to change to:

“1”

=

2400

“2”

=

4800

“3”

=

9600

“4”

=

19200

“5”

=

38400

“6”

=

57600

(MAS-6200)


The IT-R4S will respond to this request with a status message.