Flowserve Limitorque Master Station III User Manual
Page 48
Limitorque Master Station III FCD LMENIM5001-02 – 12/13
48
Table 8.4 - Register Definitions (continued)
Register #
Description
Meaning
13
Digital Inputs 2
Value of 16 Digital Inputs
Bit 0 Analog board 1 present
Bit 1 Analog board 2 present
Bit 2 Analog Input 1 lost
Bit 3 Analog Input 2 lost
Bit 4 Network Channels A/B timed out
Bit 5 Relay board R5-R8 present
Bit 6 DDC board present
Bit 7 Relay board R1-R4 and RM present
Bit 8 Foundation Fieldbus board present
Bit 9 Profibus PA board present
Bit 10 CSE chosen for input 2
Bit 11 DeviceNet board present
Bit 12 Phase lost
Bit 13 Phase reverse
Bit 14 Not Used
Bit 15 Profibus DP board present
14
Compartment Temp
Internal compartment temperature
1
15
Torque
Torque Value (0-100% unit rating)
16
Current State
Bits 0-15 Not Used
17
Field Unit Holding Register
Special Applications Only
18
Field Unit Holding Register
Special Applications Only
19
Field Unit Holding Register
Special Applications Only
20
Field Unit Holding Register
Special Applications Only
21
Field Unit Holding Register
Special Applications Only
22
Field Unit Holding Register
Special Applications Only
23
Field Unit Holding Register
Special Applications Only
24-44
Reserved
Special Applications Only
45-47
Not Named
Special Applications Only
48
TP_START_POSITION
Special Applications Only
49
TP_STOP_POSITION
Special Applications Only
50
TP_SAMPLE
Special Applications Only
51
TP_MID_T_HIGH
Special Torque Applications Only
52
TP_MID_T_POS
Special Applications Only
53
TP_MID_T_AV_VAL
Special Torque Applications Only
54
TP_STOP_VAL
Special Applications Only
55
TP_BEFORE_ MID_T_HIGH
Special Torque Applications Only
56
TP_AFTER_ MID_T_HIGH
Special Torque Applications Only
Note 1: Range is +90°C to -55°C. High byte 00 indicates positive (+) and 01 indicates negative (-). Low byte
indicates temperature value.