Limitorque Master Station III FCD LMENIM5001-02 – 12/13

42

Table 8.1 - Status Bit Definitions (continued)

Bit Number

Modbus

Bit

Address

MX/DDC

145

144

Open inhibit active

146

145

Close inhibit active

147

146

Not used

148

147

Not used

149

148

One or more phases is missing

150

149

Reverse phase sequence is occurring

151

150

ESD conflict

152

151

Inhibit conflict

153

152

Use in local/stop (input must be set for CSE and enabled)

154

153

Not used

155

154

Network emergency shutdown (ESD) is active

156

155

Local emergency shutdown is active

157

156

Field unit microprocessor has reset since the last poll

158

157

MX in stop move

159

158

Opening in local mode

160

159

Closing in local mode

161

160

Close contactor (interlocked)

162

161

Open contactor (interlocked)

163

162

S1 or R1 (opt)

164

163

S2 or R2 (opt)

165

164

R3 (opt)

166

165

R4 (opt)

167

166

R5 (opt)

168

167

R6 (opt)

169

168

R7 (opt)

170

169

Network relay

171

170

R8 (opt)

172

171

Not used

173-176

172-175

Mov series (0=1, A=9)

177

176

Remote switch

178

177

Thermal overload

179

178

Open torque switch

180

179

Open limit switch

181

180

Close torque switch

182

181

Close limit switch