Temperature/digital curve, Trial operation & troubleshooting, Relevant instructions – Delta Electronics Temperature Measurement Module DVP04PT-H2 User Manual

Page 2

background image

2. CR#1, CR#10, CR#11, CR#16, CR#17, CR#22, CR#23, CR#28 and CR#29 are reserved.

3. CR#2 ~ CR#5: The times to average the temperatures measured at CH1 ~ CH4. Range: K1 ~ K20. Default =

K10. Please note that the average times set in CR#2 ~ CR#5 need to be written in only once.

4. CR#6 ~ CR#9: The average Celsius temperature measured at CH1 ~ CH4 obtained from the average time

settings in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#6 ~ CR#9 will be the

average of the most recent 10 temperature signals in Celsius at CH1 ~ CH4.

5. CR#12 ~ CR#15: The average Fahrenheit temperature measured at CH1 ~ CH4 obtained from the average time

settings in CR#2 ~ CR#5. For example, if the average time is set as 10, the content in CR#12 ~ CR#15 will be

the average of the most recent 10 temperature signals in Fahrenheit at CH1 ~ CH4.

6. CR #18 ~ CR #21: Displaying the present temperature in Celsius at CH1 ~ CH4

7. CR #24 ~ CR #27: Displaying the present temperature in Fahrenheit at CH1 ~ CH4

8. CR #30: Error status (see the table below):

Error status

Content

b15 ~ b8

b7

b6

b5

b4

b3

b2

b1

b0

Abnormal

power

supply K1(H’1)

0 0 0 0 0 0 0 1

Scale exceeds the range
or wiring to empty external
contact

K2(H’2)

0 0 0 0 0 0 1 0

Incorrect

mode

setting K4(H’4)

0 0 0 0 0 1 0 0

OFFSET/GAIN

error K8(H’8)

0 0 0 0 1 0 0 0

Hardware malfunction

K16(H’10)

0 0 0 1 0 0 0 0

Abnormal digital range

K32(H’20)

0 0 1 0 0 0 0 0

Incorrect average times
setting

K64(H’40)

0 1 0 0 0 0 0 0

Instruction error

K128(H’80)

reserved

1 0 0 0 0 0 0 0

Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the same time.

0 = normal; 1 = error

9. CR#31: The setting of RS-485 communication address. Range: 01 ~ 255. Default = K1.

10. CR#32: The setting of RS-485 communication speed. b0: 4,800bps; b1: 9,600bps (default); b2: 19,200bps; b3:

38,400bps; b4: 57,600bps; b5: 115,200bps; b6 ~ b13: reserved; b14: high/low bit exchange of CRC checksum

(only valid in RTU mode); b15: switching between ASCII mode and RTU mode.

11. CR#33: b0 ~ b11: For returning the CR settings to default settings.

b12 ~ b15: ERR LED definition. Default: b12 ~ b15 = 1111.

12. CR#34: Firmware version of the model.

13. CR#35 ~ CR#48: Parameters for system use.

14. CR#0 ~ CR#34: The corresponding parameter address H’4064 ~ H’4086 are for users to read/write data by

RS-485 communication. When using RS-485, the user has to separate the module with MPU first.

a. Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps.

b. Modbus ASCII/RTU communication protocol: ASCII data format (7-bit, Even bit, 1 stop bit (7, E, 1)); RTU

data format (8-bit, Even bit,1 stop bit (8, E, 1)).

c. Function: H’03 (read register data); H’06 (write 1 word datum into register); H’10 (write many word data into

register).

d. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written by

MPU through TO/DTO instruction.

Temperature/Digital Curve

Celsius temperature measurement mode

+6000

+3000

-2000

+600

-200 C

C

Digital output

Measured temperature input



Fahrenheit temperature measurement mode

+11,120

+5,560

-3,280

+1,112

-328 F

F

Digital output

Measured temperature input

Trial Operation & Troubleshooting

™

LED Display

1. When the module is powered for the first time, POWER LED will be on and ERROR LED will be on for

0.5 second. After this, A/D LED will start to flash.

2. When the power supply is normal, POWER LED will be on and ERROR LED should be off. When the

power supply is less than 19.5V, ERROR LED will keep being on until the power supply goes higher

than 19.5V.

3. When series connected with PLC MPU, the RUN LED on the MPU will be on and A/D LED will flash.

4. When controlled by RS485, RS-485 LED on the module will flash after receiving the RS-485 instruction.

5. When the input or output value exceeds the upper bound or falls below the lower bound after conversion,

ERROR LED will flash.

™

Program Example

M1000

FROM

K0

= H 6402 D0

'

TO

K0

FROM

K0

FROM

K0

FROM

K0

FROM

K0

END

M1002

K0

K2

K6

K12

K18

K24

D0

D10

D20

D24

D30

D34

K1

K4

K4

K4

K4

K4

Read the model name from K0 and see if it is DVP04PT-H2: H’6402

Set the average times in CH1 ~ CH4 as D10 ~ D13.

If D0 = H’6402, read the average temperature (°C) measured in CH1 ~ CH4 from CR#6 ~ CR#9 and store the 4

data in D20 ~ D23.

Read the average temperature (°F) measured in CH1 ~ CH4 from CR#12 ~ CR#15 and store the 4 data in D24~

D27.

Read the average temperature (°C) measured in CH1 ~ CH4 from CR#18 ~ CR#21and store the 4 data in D30~

D33.

Read the average temperature (°F) measured in CH1 ~ CH4 from CR#24 ~ CR#27 and store the 4 data in D34~

D37.

Relevant Instructions

API

78

D

F R O M

P

Read CR data in special modules

Instruction
Explanation

: No. of special module (m1 = 0 ~ 7)

: CR# in special module to be read

: Device for storing read data

: Number of data to be read at a time

Program
Example

Read CR#24 of special module No. 0 into D0 and CR#25 into D1. Only 2 groups of data are
read at a time (n = 2).

X0

FROM

K0

K24

D0

K2


API

79

D

T O

P

Write CR data into special module

Instruction
Explanation

: No. of special module (m1 = 0 ~ 7)

: CR# in special module to be written

: Data to be written into CR

: Number of data to be written at a time

Program
Example

Use 32-bit instruction DTO to write the content in D11 and D10 into CR#7 and CR#6 of special
module No. 0. Only 1 group of data is written in at a time (n = 1).

X0

DTO

K0

K6

D10

K1

Remarks

Operand rules

1.

: The No. of special modules connected to PLC MPU. No. 0 is the module closest to te

MPU. Maximum 8 modules are allowed to connected to a PLC MPU and they will not occupy

any I/O points.

2.

: CR#. CR (control register) is the 49 16-bit memories built in the special module,

numbered in decimal as #0 ~ #48. All operation status and settings of the special module are

contained in the CR.

3. FROM/TO instruction is for reading/writing 1 CR at a time. DFROM/DTO instruction is for

reading/writing 2 CRs at a time.

CR #10

CR #9

L ower 1 6- bi t

Desig nated CR number

Hi gher 16 -b it

4. Number of groups “n” to be transmitted: n = 2 in 16-bit instructions and n = 1 in 32-bit

instructions mean the same.

D0
D1
D2
D3
D4
D5

CR #5
CR #6
CR #7
CR #8
CR #9
CR #10

D0
D1
D2
D3
D4
D5

CR #5
CR #6
CR #7
CR #8
CR #9
CR #10

Designated device

Designated CR

Designated device Designated CR

16-bit instruction when n=6

32-bit instruction when n=3

M1083 for switching instruction modes in EH2 series models

1. When M1083 = Off, during the execution of FROM/TO instruction, all external or internal

interruption subroutines will be forbidden. The interruptions are allowed only after FROM/TO

instruction finishes its execution. FROM/TO instruction can also be used in an interruption

subroutine.

2. When M1083 = On and an interruption signal occurs during the execution of FROM/TO

instruction, the interruption will be processed first (with a 100us delay) and the execution of

FROM/TO will be stopped. After the interruption subroutine finishes its execution, the

program will jump to the next instructio of FROM/TO. FROM/TO cannot be used in an

interruption subroutine.