Temperature Measurement Module

Instruction Sheet

Warning

9

Please read this instruction sheet carefully before use.

9

Switch off the power before wiring.

9

DVP04PT-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust, humidity,

electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or
specific tools are required to open the enclosure) in case danger and damages on the device may occur.

9

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the

wiring again before switching on the power.

9

Do NOT touch any terminal when the power is switched on.

9

Make sure the ground termnial

is correctly grounded in order to prevent electromagnetic interference.

9

Use wires with resistance when connect the platinum resistance thermister (RTD) to PLC.

9

Keep the wire as short as possible between RTD and PLC and the power wire as far away as possible from I/O wire to

prevent interference.

Introduction

1.1 Model Explanation & Peripherals

™

Thank you for choosing Delta’s DVP series. DVP04PT-H2 is able to receive 4 points of platinum temperature
sensors (PT100 3-WIRE 100Ω 3850 PPM/

°C (DIN 43760 JIS C1604-1989)) and convert them into 14-bit digital

signals. Besides, through FROM/TO instructions in DVP-EH2 MPU program, DVP04PT-H2 is able to read and
write the data in the module. There are 49 16-bit control registers (CR) in DVP04PT-H2.

™

DVP04PT-H2 displays temperatures in Celsius (resolution: 0.1°C) and Fahrenheit (resolution: 0.18°F).

™

Nameplate Explanation

04 PT-H20 T6 500 001

VX.XX

24Vdc 2.5W

MADE IN XXXXX X

D e l t a P L C m o d e l n a m e

14 BITS

PT100

B a r c o d e , s e r i a l N o . , Ve r s i o n

P o w e r i n p u t s p e c i f i c a t i o n

A n a l o g I / O m o d u l e s p e c i f i c a t i o n

™

Model/Serial No. Explanation

DVP series

AD: Analog input
DA: Analog output

PT: Temperature measurement (PT-100)
TC: Temperature measurement

(thermocouple)

Points (input + output)

Model type

XA: Mixed analog I/O

HC: High-speed counter input

PU: Single-axis position control

H: For EH series MPU
H2: For EH2 series MPU

Model name

Production No.
Production week
Production year (2006)
Production plant (Taoyuan)
Version No.

1.2 Product Profile (Indicators, Terminal Block, I//O Terminals)

Unit: mm

D

-

L

+

L

-

L

+

24V

0V

L

-

L

+

L

-

L

+

L

-

D +

I -

8

CH
1

C

H

2

CH
3

C

H

4

RS
-4

8

5

F

G

I -

F

G

I -

F

G

I -

1

DIN rail (35mm)

6

Terminals

2

Connection port for extension unit/module

7

Mounting hole

3

Model name

8

I/O terminals

4

POWER, ERROR, A/D indicator

9

Mounting port for extension unit/module

5

DIN rail clip

1.3 External

Wiring

PT100

CH1

CH4

1mA

DC/DC

5V

AG

+15V

-15V

AG

AG

AG

24+

0V

FG

I-

L-

L+

FG

I-

L-

L+

*2

*3

1mA

Shielding
cable *1

Shielding

cable *1

Terminal of
power module

Converter

System
grounding

Earth
(100 or less)

PT100

*1: Wiring for analog input should adopt cables of PT100 temperature sensor or double shielding cable and should be

separated from other power cables that may cause interference. Please use 3 wires for PT100.

*2: Terminal FG is the ground location for noise suppression.
*3: Please connect the

terminal on both the power module and DVP04PT-H2 to the system earth point and ground the

system contact or connect it to the cover of power distribution cabinet.

Note: DO NOT wire empty terminal

.

Specifications

2.1. Functions

Temperature measurement

(04PT) module

Celsius (°C)

Fahrenheit (°F)

Power supply voltage

24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%)

Analog output channel

4 channels/module

Applicable sensor
types

3-WIRE PT100Ω 3850 PPM/°C (DIN 43760 JIS C1604-1989)

Current excitation

1mA

Range of input
temperature

-200 ~ 600

-328 ~ 1112

Range of digital
conversion

K-2,000 ~ K6,000

K-3,280 ~ K11,120

Resolution

14 bits (0.1)

14 bits (0.18)

Output impedance

0.5Ω or less

Overall accuracy

±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F

Response time

200 ms × the number of channels

Isolation

Isolation between digital area and analog area. No isolation among channels.

Digital data format

13 significant bits out of 16 bits are available; in 2’s complement.

Average function

Yes; available for setting up in CR#2 ~ CR#5; range: K1 ~ K20

Self-diagnosis

Upper and lower bound detection/channel

Protection

The voltage output is protected by short circuit. Please also be aware that being short
circuit for too long period of time may cause damage on internal circuit. The current
output can be open circuit.

Communication mode
(RS-485)

ASCII/RTU mode.
Communication speed: 4,800/9,600/19,200/38,400/57,600 /115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1)

RS-485 cannot be used when connected to PLC MPU.

When connected to
DVP-PLC MPU in
series

The modules are numbered from 0 to 7 automatically by their distance from MPU. No.
0 is the closest to MPU and No. 7 is the furthest. Maximum 8 modules are allowed to
connect to MPU and will not occupy any digital I/O points.

2.2. Others

Power Supply

Max. rated power
consumption

24 VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%), 2.5W supplied by external power

Environment

Operation/storage

Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -40°C ~ 70°C (temperature); 5 ~ 95% (humidity)

Vibration/shock
immunity

International standard: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27
(TEST Ea)

Control Registers

DVP04PT-H2

Description

CR

#

RS-485

Parameter

address

Latched

Register content

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

#0

H’4064 ○ R

Model name

Set up by the system. DVP04PT-H2 = H’6402

#1

Reserved

#2

H’4066 ○

R/W CH1 average time

#3

H’4067 ○

R/W CH2 average time

#4

H’4068 ○

R/W CH3 average time

#5

H’4069 ○

R/W CH4 average time

Range of settings in CH1 ~ CH4: K1 ~ K20
Default = K10

#6

H’406A ╳ R

Average °C temp.
measured at CH1

#7

H’406B ╳ R

Average °C temp.
measured at CH2

#8

H’406C ╳ R

Average °C temp.
measured at CH3

#9

H’406D ╳ R

Average °C temp.
measured at CH4

Average Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C

#10 ~ #11

Reserved

#12 H’4070 ╳ R

Average °F temp.
measured at CH1

#13 H’4071 ╳ R

Average °F temp.
measured at CH2

#14 H’4072 ╳ R

Average °F temp.
measured at CH3

#15 H’4073 ╳ R

Average °F temp.
measured at CH4

Average Fahrenheit temperature measured at CH1 ~ CH4.
Unit: 0.1°F

#16 ~ #17

Reserved

#18 H’4076 ╳ R

Present °C temp.
measured at CH1

#19 H’4077 ╳ R

Present °C temp.
measured at CH2

#20 H’4078 ╳ R

Present °C temp.
measured at CH3

#21 H’4079 ╳ R

Present °C temp.
measured at CH4

Present Celsius temperature measured at CH1 ~ CH4.
Unit: 0.1°C

#22 ~ #23

Reserved

#24 H’407C ╳ R

Present °F temp.
measured at CH1

#25 H’407D ╳ R

Present °F temp.
measured at CH2

#26 H’407E ╳ R

Present °F temp.
measured at CH3

#27 H’407F ╳ R

Present °F temp.
measured at CH4

Present Fahrenheit temperature measured at CH1 ~ CH4.
Unit: 0.1°F

#28 ~ #29

Reserved

#30 H’4082 ╳ R

Error status

Register for storing all error status. See the table of error status for more
information.

#31 H’4083 ○ R/W

Communication address
setting

For setting RS-485 communication address. Range: 01 ~ 255
Default = K1

#32 H’4084 ○

R/W

Communication speed
(Baud Rate) setting

For setting up communication speed:
4,800/9,600/19,200/38,400/57,600/115,200 bps
ASCII data format: 7-bit, Even bit, 1 stop bit (7, E, 1)
RTU data format: 8-bit, Even bit, 1 stop bit (8, E, 1) Default = H’0002
b0: 4,800 bps b1: 9,600 bps (default)
b2: 19,200 bps b3: 38,400 bps
b4: 57,600 bps b5: 115,200 bps
b6 ~ b13: reserved
b14: High/low bit exchange of CRC checksum (only valid in RTU mode)
b15: Switch between ASCII/RTU modes; 0 = ASCII mode (default)

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

ERR LED

CH4

CH3

CH2

CH1

#33 H’4085 ○

R/W

Returning to default
setting

Take the setting of CH1 for example:
1. b0 is reserved.
2. b1 is reserved.
3. When b2 is set as 1, all the settings will return to default settings.
ERR LED definition: default of b12 ~ b15 = 1111
1. b12 corresponds to CH1. When b12 = 1 or the scale exceeds the range,

ERR LED will flash.

2. b13 corresponds to CH2. When b13 = 1 or the scale exceeds the range,

ERR LED will flash.

3. b14 corresponds to CH3. When b14 = 1 or the scale exceeds the range,

ERR LED will flash.

4. b15 corresponds to CH4. When b15 = 1 or the scale exceeds the range,

ERR LED will flash.

#34 H’4086 ○

R

Firmware version

Displaying the current firmware version in hex; e.g. version 1.0A is indicated
as H’010A

#35 ~ #48

For system use

Symbols

: latched (when written in through RS-485 communication)

: non-latched

R: Able to read data by FROM instruction or RS-485 communication
W: Able to write data by TO instruction or RS-485 communication

Explanations:
1. CR#0: Model name. The user can read the model name from the program and see if the extension module

exists.