Flowserve Logix 1200e LGAIM0044 User Manual
Page 43

Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
44-43
Erratic communications
1. Maximum cable length or
impedance exceeded
1. HART modem not receiving
enough power. (laptop batteries
low)
1. Interference with I.S. barrier
Alarms
Temperature
1. Ambient temperature has
exceeded electronics ratings
Hall sensor
1. Cable may have bad connection
1. Sensor may be damaged
Modulator Current
1. Modulator minimum pressure
may be too low
1. Clogged orifice
1. Bad cable connection
1. See Modulator Current Alarm
EEPROM checksum
1. Error when reading non-volatile
memory storage
Multiple Internal Flags
1. Bad micro-controller on main
PCB assembly
1. Replace main PCB assembly
LEDs
LED alternates between Green and
Red in normal operation
1. Modulator coil current may be
too high
1. Supply pressure may be close
to minimum of 30 psig (2.1 barg)
1. See Modulator Current Alarm
No LED blinks during calibration
1. Normal operation
1.
Yellow LED is blinking but valve posi-
tion is fine
1. User-defined limit may have
been reached; check alarm
screen
Red LED is blinking on advanced
model, even though positioner has
pressure
1. Pressure below 30 psi (2.1 bar)
Advanced Features
Will not display pressure readings
1. Configuration not set to
Advanced
MPC will not function
1. Lower soft limit >= 0%.
1. 1% hysteresis around MPC set-
point being considered
Table IV: Troubleshooting Logix 1200 Digital Positioner (3 of 3)
Failure or Problem
Probable Cause(s)
Refer to Section(s)