7 limit switch specifications, 8 positioner performance characteristics, 9 physical specifications – Flowserve 500+ Series Logix User Manual
Page 9: 10 temperature, 11 valvesight dtm software specifications, Imit, Witch, Pecifications, Ositioner, Erformance

User Instructions - Logix® 500+ Series Digital Positioners FCD LGENIM0105-10 11/13
flowserve.com
9
2.7
Limit Switch Specifications
Table 7: Limit Switch Specifications
For entity parameters, see section 3 HAZARDOUS AREA
CERTIFICATIONS.
Switch
Specifications
Mechanical
Cherry DG 13-B(X)RA
NO and/or NC
General Purpose Only
Load Current:
3/2 AAC/ADC
Voltage:
125/30 VAC/VDC
Temperature:
-25 to +85 °C
(-13 °F to 185 °F)
Reed
Hamlin 59050-030
NO
Load Current: 500 mA
Voltage:
200VDC
Temperature:
-40 to +105 °C
(-40 °F to 221 °F)
Inductive Sensor
P&F NJ2-V3-N
NAMUR NC -3
Load Current:
Plate: ≤ 1 mA;
No Pla
te: ≥ 3 mA
Voltage:
Nominal 8.2 VDC
Temperature:
-25 °C to 100 °C
(-13 °F to 212 °F)
Inductive Proximity
P&F SJ2-S1N
NAMUR NO-4
Load Current:
Plate: ≤ 1 mA;
No Plate: ≥ 3 mA
Voltage:
5-25 VDC
(Nominal 8 VDC)
Temperature:
-25 °C to 100 °C
(-13 °F to 212 °F)
Inductive Proximity
P&F SJ2-SN
NAMUR NC-5
Load Current:
Plate: ≤ 1 mA;
No Plate: ≥ 3 mA
Voltage:
5-25 VDC
(Nominal 8 VDC)
Temperature:
-40 °C to 100 °C
(-40 °F to 212 °F)
Inductive Sensor
P&F NBB2-V3-E2
PNP NO
General Purpose Only
Load Current:
0…100 mA
Voltage:
10...30 VDC
Temperature:
-25 °C to 70 °C
(-13 °F to 158 °F)
2.8
Positioner Performance
Characteristics
Table 8: Performance Characteristics
Better than or equal to the following values on a 25 square inch
Mark I actuator.
Resolution
≤ 0.25%
Linearity
+/-1.25%
Repeatability
≤ 0.25%
Hysteresis
≤ 1.0%
Deadband
≤ 0.3%
Sensitivity
≤ 0.25%
Stability
≤ 0.4%
Long term drift
≤ 0.5%
Supply Pressure Effect
≤ 0.2%
NOTE: Performance tested according to ISA 75.13.
2.9
Physical Specifications
Table 9: Physical Specifications
For dimensions, see section 19 POSITIONER .
Housing Material
Cast, powder-painted aluminum
EN AC-AlSi12(Fe)
Soft Goods
Fluorosilicone
Weight of Base
Positioner Without
Accessories
With Single Acting Relay
1.76 kg (3,88 lb)
With Double Acting Relay
1.88 kg (4.14 lb)
2.10 Temperature
Table 10: Temperature
Operating Temperature
Range
-52 to 85°C (-61.6 to 185°F)
Transport and Storage
Range
-52 to 85°C (-61.6 to 185°F)
NOTE: Reduced performance possible at low
temperatures.
2.11 ValveSight DTM Software
Specifications
Table 11: ValveSight DTM Software Specifications
Computer
Minimum Pentium processor running
Windows 95, 98, NT, 2000, XP, 7, 32 MB
total memory (64 MB recommended), 30
MB available hard disk space, CD-ROM
drive
Ports
1 minimum available with 8 maximum
possible. (Can also communicate via
serial, PCMCIA and USB connections)
HART Modem
RS-232,
PCMCIA card, or
USB
HART Filter
May be required in conjunction with some
DCS hardware.
HART MUX
MTL 4840/ELCON 2700