User Instructions - Logix® 500+ Series Digital Positioners FCD LGENIM0105-10 11/13
flowserve.com
10
3 HAZARDOUS AREA CERTIFICATIONS
DANGER: Certifications listed on the positioner are correct for that positioner. Before using the information on this page,
ensure the certifications on the positioner label match the certifications on this page.
Table 12: Logix 500+ Series Hazardous Locations Information
ATEX
Intrinsically Safe
FM12ATEX0009X
II 1 G
Ex ia IIC Ga T4/T6
T4 Tamb = -20
˚C ≤ Ta ≤ +85˚C
T6 Tamb = -
52˚C ≤ Ta ≤ +45˚C
IP 66
Entity
Parameters
4-20
Input
MFC
Limit
Switches
Remote
Mount
-02
Ui (Vdc)=
30
30
10.6
Vo = 5V
Ii (mA)=
100
100
29.7
Io = 79mA
Pi (mW)=
800
800
79
Po = 129mW
Ci (nF)=
0
0
1
Co = 2uF
Li (µH)=
47
0
1
Lo = 100uH
North America (cFMus)
Intrinsically Safe
Class I, Div 1, Groups A,B,C,D
Class I, Zone 0, AExia IIC (US)
Class I, Zone 0, Ex ia IIC (Canada)
T4 Tamb = -20
˚C ≤ Ta ≤ +85˚C
T6 Tamb = -
52˚C ≤ Ta ≤ +45˚C
Type 4X
Entity
Parameters
4-20
Input
MFC
Limit
Switches
Remote
Mount
-02
Ui (Vdc)=
30
30
10.6
Vo = 5V
Ii (mA)=
100
100
29.7
Io = 79mA
Pi (mW)=
800
800
79
Po = 129mW
Ci (nF)=
0
0
1
Co = 2uF
Li (µH)=
47
0
1
Lo = 100uH
Non-Incendive
Class I, Div 2, Groups A,B,C,D,
T4 Tamb = -20
˚C ≤ Ta ≤ +85˚C
T6 Tamb = -
52˚C ≤ Ta ≤ +45˚C
Type 4X
Barriers Not Required when installed per the NEC/CEC
IECEx
Intrinsically Safe
FMG 12.0001X
Ex ia IIC Ga T4/T6
T4 Tamb = -20
˚C ≤ Ta ≤ +85˚C
T6 Tamb = -
52˚C ≤ Ta ≤ +45˚C
IP 66
Entity
Parameters
4-20
Input
MFC
Limit
Switches
Remote
Mount
-02
Ui (Vdc)=
30
30
10.6
Vo = 5V
Ii (mA)=
100
100
29.7
Io = 79mA
Pi (mW)=
800
800
79
Po = 129mW
Ci (nF)=
0
0
1
Co = 2uF
Li (µH)=
47
0
1
Lo = 100uH
Notes
•
Reference installation drawing # 291780
Warning!
•
Limit Switch options -01, -03, -04, -05, -06 are not rated for
use in hazardous areas. Select these options only when
installing in non-explosive atmospheres.
•
Covers must be properly installed in order to maintain
environmental ratings.
Special Conditions for Safe Use:
•
The equipment must be installed in such a manner as to
minimize the risk of impact or friction with other metal
surfaces.
•
To avoid possibility of static discharge clean only with a
damp Cloth
•
For Intrinsically Safe installations the positioner must be
connected to suitably rated intrinsically safe equipment,
and must be installed in accordance with applicable
intrinsically safe installation standards.
•
Substitution of components may impair Intrinsic Safety.
•
Use appropriately rated cable insulation at higher
temperatures.
Conditions spéciales pour une utilisation en toute sécurité:
•
Le matériel doit être installé de sorte à réduire au minimum le risque de choc ou de frottement avec d'autres surfaces métalliques.
•
Pour éviter les risques de décharge d'électricité statique Nettoyez uniquement avec un chiffon humide
•
Pour les installations en sécurité intrinsèque, le positionneur doit être connecté à un équipement sécurité intrinsèque
convenablement qualifié, et doit être installé conformément aux normes d'installation sécurité intrinsèque applicables.
•
La substitution de composants peut compromettre la sécurité intrinsèque.
•
Utiliser une isolation appropriée du câble à des températures plus élevées.