Atex marking (1.6.4.2), Compliance, atex (1.6.4.1) – Flowserve CPX IDP User Manual
Page 6

CPX, CPXR, CPXN and CPXP USER INSTRUCTIONS ENGLISH 71569117 09-11
Page 6 of 44
flowserve.com
If the temperature is greater than 80 ºC (175 ºF) or 
below -5 ºC (23 ºF) in a restricted zone, or exceeds 
local regulations, action as above shall be taken. 
HAZARDOUS LIQUIDS
When the pump is handling hazardous liquids care 
must be taken to avoid exposure to the liquid by 
appropriate siting of the pump, limiting personnel 
access and by operator training. If the liquid is 
flammable and or explosive, strict safety procedures 
must be applied. 
 
Gland packing must not be used when pumping 
hazardous liquids. 
PREVENT EXCESSIVE EXTERNAL
PIPE LOAD 
Do not use pump as a support for piping. Do not mount 
expansion joints, unless allowed by Flowserve in writing, 
so that their force, due to internal pressure, acts on the 
pump flange. 
NEVER RUN THE PUMP DRY
ENSURE CORRECT LUBRICATION
(See section 5, Commissioning, startup, operation and 
shutdown.) 
ONLY CHECK DIRECTION OF
MOTOR ROTATION WITH COUPLING ELEMENT/ 
PINS REMOVED 
Starting in reverse direction of rotation will damage the 
pump. 
START THE PUMP WITH OUTLET
VALVE PART OPENED 
(Unless otherwise instructed at a specific point in the 
User Instructions.) 
This is recommended to minimize the risk of 
overloading and damaging the pump or motor at full or 
zero flow. Pumps may be started with the valve further 
open only on installations where this situation cannot 
occur. The pump outlet control valve may need to be 
adjusted to comply with the duty following the run-up 
process. (See section 5, Commissioning start-up, 
operation and shutdown.) 
INLET VALVES TO BE FULLY
OPEN WHEN PUMP IS RUNNING 
Running the pump at zero flow or below the 
recommended minimum flow continuously will cause 
damage to the pump and mechanical seal. 
DO NOT RUN THE PUMP AT
ABNORMALLY HIGH OR LOW FLOW RATES 
Operating at a flow rate higher than normal or at a flow 
rate with no back pressure on the pump may overload 
the motor and cause cavitation. Low flow rates may 
cause a reduction in pump/bearing life, overheating of 
the pump, instability and cavitation/vibration. 
 
1.6.4 Products used in potentially explosive 
atmospheres 
Measures are required to:
Avoid excess temperature
Prevent build up of explosive mixtures
Prevent the generation of sparks
Prevent leakages
Maintain the pump to avoid hazard
 
The following instructions for pumps and pump units 
when installed in potentially explosive atmospheres 
must be followed to help ensure explosion protection. 
For ATEX, both electrical and non-electrical equipment 
must meet the requirements of European Directive 
94/9/EC. Always observe the regional legal Ex 
requirements eg Ex electrical items outside the EU may 
be required certified to other than ATEX eg IECEx, UL. 
 
1.6.4.1 
Scope of compliance
Use equipment only in the zone for which it is
appropriate. Always check that the driver, drive 
coupling assembly, seal and pump equipment are 
suitably rated and/or certified for the classification of the 
specific atmosphere in which they are to be installed. 
 
Where Flowserve has supplied only the bare shaft 
pump, the Ex rating applies only to the pump. The 
party responsible for assembling the ATEX pump set 
shall select the coupling, driver and any additional 
equipment, with the necessary CE Certificate/ 
Declaration of Conformity establishing it is suitable for 
the area in which it is to be installed. 
 
The output from a variable frequency drive (VFD) can 
cause additional heating effects in the motor and so, 
for pumps sets with a VFD, the ATEX Certification for 
the motor must state that it is covers the situation 
where electrical supply is from the VFD. This 
particular requirement still applies even if the VFD is 
in a safe area. 
