Set alarm thresholds – Dataprobe T-APS Rack User Manual

Page 16

background image

Set Alarm Thresholds

Set LCV Threshold (Alarm)

Set Line Code Violation Error Ratio

1E-7 = 1 x 10

-7

5E-6 = 5 x 10

-6

1E-5 = 1 x 10

-5

1E-4 = 1 x 10

-4

1E-3 = 1 x 10

-3

Once the Line Code Violation Error Ratio exceeds the preset threshold value, it will then switch
the ACTIVE PATH to the PROTECTION PATH.

Set LCV Threshold (Cleared)

Set Line Code Violation Alarm Clear Ratio

1E-9 = 1 x 10

-9

1E-8 = 1 x 10

-8

1E-7 = 1 x 10

-7

1E-6 = 1 x 10

-6

1E-5 = 1 x 10

-5

Once the Line Code Violation Clear Ratio achieves the preset threshold value, it will then
switch back from PROTECTION PATH to the ACTIVE PATH.