beautypg.com

Dataprobe iBoot-G2 Operation Manual User Manual

Page 27

background image

V140506E

iBoot-G2+

Page 27

Device Commands

Set commands are available to the administrator only

set location <20 char. max>
get location

This command is used to set the iBoot-

G2’s location ID.

Get returns the current setting

New Boot

set cycle <1-999>
get cycle

This command sets the cycle time in seconds
Get returns the current setting

5

set delay <0-999>
get delay

This command sets the delay time in seconds
Get returns the current setting

1

set timeout <0-99>
get timeout

This command sets the auto logout time in minutes
Get returns the current setting

2

set

initial state off | last>
get initial state

This command sets the initial state of the outlet when the
iBoot-G2 is initially powered up

Last

set upgrade enable

Enables or disables the ability to upload new firmware to
the iBoot-G2.

no

login

Prompts for admin credentials when logged in as user

logout

Terminates the session

reboot

This command reboots the iBoot-G2.

Graceful Shutdown Commands

Set commands are available to the administrator only

Get gsd

This command returns all the current settings for
Graceful Shutdown

set gsd

enabled

This command enables or disables the shutdown delay
process.

no

set gsd

ipaddress

This command is used to set IP address of the target
system for graceful shutdown.

set gsd

username
<20 char. max>

This command sets username of the target system

set gsd

password
<20 char. max>

This command sets the password of the target system

set gsd


shutdowndelay <0-999>

This command sets the shutdown delay in seconds

set gsd

rebootdelay
<0-999>

This command sets the reboot delay in seconds


This manual is related to the following products: