4.12 Troubleshooting
This sub-section contains some symptoms that you may encounter in the signs. This list does not
include every possible symptom, but does represent common situations that may occur.
Symptom/Condition
Possible Cause/Remedy
One or more LEDs on a single module
fail to light.
•
Replace pixel strip
•
Replace/check cables on the module.
•
Replace the driver.
One or more LEDs on a single module
fail to turn off.
•
Replace pixel strip
•
Replace/check cables on module.
•
Replace the driver.
A section of the sign is not working. The
section extends all the way to the right
side of the sign.
•
Replace the first driver on the left side of the
first module that is not working.
•
Replace the second driver that is not
working.
•
Replace the power supply assembly on the
first module that is not working.
•
Replace the ribbon cable.
One row of modules does not work or is
garbled.
•
Replace first driver.
•
Replace controller.
•
Check the fuses in the power termination
box.
A group of modules, which share the
same power supply assembly, fail to
work.
•
Replace the power supply assembly.
•
Check power supply voltage
Entire sign fails to work.
•
Check for proper line voltage into the power
termination panel.
•
Check/replace the signal cable to the
controller.
•
Check/replace the ribbon cable from the
controller to the driver.
•
Check the voltage settings on the power
supplies.
•
Replace the controller.
•
Verify proper use of the software in the
operation manual.
Temperature always reads 32 degrees
F/0 degrees C
•
Check temperature sensor connections.
•
Replace the temperature sensor.
•
Replace the controller.
Sign is stuck on bright or dim.
•
Check Manual/Auto dimming in Venus 1500
software.
•
Check light detector cable.
•
Check light detector for obstructions.
•
Replace the light detector.
•
Replace the controller.