Product overview

Technical data

Technical data

EL9540

EL9550

Function

surge filter field supply

surge filter system and field supply

Nominal voltage

24 V (­15 %/+20 %)

Surge filter field supply

yes

Surge filter system supply

­

yes

Diagnostics

­

Reported to E­Bus

­

PE contact

yes

­

Shield connection

­

Current consumption E­bus

­

Bit width in the process image 0

Connection to mounting rail

­

Electrical isolation

­

Side by side mounting on
EtherCAT Terminals with
power contact

yes

­

Side by side mounting on
EtherCAT Terminals without
power contact

yes

Dimensions (B x H x T)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Configuration

no address­ or configuration setting necessary

Weight

approx. 50 g

Permissible ambient
temperature range (during
operation)

­25°C ... +60°C (extended temperature range)
0°C ... +55°C (according to cULus [

}

 74] for Canada and USA)

0°C ... +55°C (according to ATEX [

}

 71], see special conditions [

}

 71])

Permissible ambient
temperature range (during
storage)

­40°C ... +85°C

Permissible relative humidity

95%, no condensation

Mounting [

}

 60]

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

conforms to EN 60068­2­6/EN 60068­2­27

EMC resistance burst/ESD

conforms to EN 61000­6­2/EN 61000­6­4

Protect. class

IP 20

Installation pos.

variable, see chapter "Mounting of Passive Terminals [

}

 70]"

Approval

CE
ATEX [

}

 71]

cULus [

}

 74]

LEDs and connection EL9540

LED

Color

Meaning

Power­LED

green

off

24 V

DC

 field supply not present

on

24 V

DC

 field supply present

EL9xxx

47

Version 3.1