BECKHOFF EL9xxx User Manual
Page 19

Product overview
Technical data
Technical data
EL9100
EL9110
EL9190
Nominal voltage
24 V
DC
variable, up to 230 V AC/
DC
Power contact current load
max. 10 A
Electrical isolation
yes
Current consumption from E
Bus
typ. 90 mA
Bit width in the process image
1 bit (diagnosis)
Configuration
no address or configuration settings
Power LED
yes
yes
no
Diagnosis
no
yes, in process image
no
Electrical connection to
mounting rail
no
PE contact
yes
Weight
approx. 50 g
Permissible ambient
temperature range (during
operation)
25°C ... +60°C (extended temperature range)
0°C ... +55°C (according to cULus [
74] for
Canada and USA)
0°C ... +55°C (according to ATEX [
71])
0°C ... +55°C
Permissible ambient
temperature range (during
storage)
40°C ... +85°C
25°C ... +85°C
Permissible relative humidity
95%, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 6006826/EN 60068227, see
Installation instructions [
mechanical load capacity
conforms to EN
6006826/EN
60068227
EMC resistance burst/ESD
conforms to EN 6100062/EN 6100064
Protect. class
IP 20
Installation pos.
variable, see chapter
"Mounting of Passive
Terminals [
70]"
variable
variable, see chapter
"Mounting of Passive
Terminals [
70]"
Approval
CE
ATEX [
CE
cULus [
Connection EL9100, EL9110, EL9190
CAUTION
Hazard to individuals and devices!
When designing a Bus Terminal block with different potentials on the power contacts (e.g.
230 V AC and 24 V DC), please note that it is mandatory to use potential separation termi
nals (EL9080)!
Bring the bus system into a safe, powered down state before starting installation, disas
sembly or wiring of the Bus Terminals!
EL9xxx
19
Version 3.1