BECKHOFF EL9xxx User Manual
Page 26

Product overview
Technical data
Technical Data
EL9181
EL9182
EL9183
Technology
Potential distribution terminal
Number of separate potentials 2
8
1
Terminal points per potential
8
2
16
Nominal voltage
≤ 60 V
DC
Current load
max. 10 A (per terminal point)
Current consumption from E
Bus
Ebus looped through
yes
Power contacts looped
through
yes (2 power contacts)
Diagnosis
Message to EBus
PE contact
no
Bit width in the process image 0
Electrical connection to
mounting rail
Electrical connection to power
contacts
Electrical isolation
Configuration
no address or configuration settings
Conductor types
solid wire, stranded wire and ferrule
Conductor connection
solid wire conductors: direct plugin technique; stranded wire conductors and
ferrules: spring actuation by screwdriver
Rated crosssection
solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75
mm²
Weight
approx.. 60 g
Permissible ambient
temperature range (during
operation)
0°C ... +55°C
Permissible ambient
temperature range (during
storage)
25°C ... +85°C
Permissible relative humidity
95%, no condensation
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
on 35 mm mounting rail conforms to EN 60715
Vibration/shock resistance
conforms to EN 6006826/EN 60068227
EMC resistance burst/ESD
conforms to EN 6100062/EN 6100064
Protect. class
IP 20
Installation pos.
variable, see chapter "Mounting of Passive Terminals [
70]"
Approval
CE
Connection EL9181
Terminal point
Meaning
Indication
No.
1 8
1 8
Terminal points 1 8 are connected internally
9 16
9 16
Terminal points 9 16 are connected internally
EL9xxx
26
Version 3.1