Led bus - fieldbus diagnosis – BECKHOFF BC3150 User Manual
Page 97
Safety Instructions
Fieldbus Components
95
Error
code
Error
argument
Description
Remedy
0
K-Bus data error, break
behind the Bus Coupler
Check whether the n+1 Bus Terminal is correctly connected;
replace if necessary.
4
n
Break behind Bus Terminal
n
Check whether the Bus End Terminal KL9010 is connected.
5
n
K-Bus error in register
communication with Bus
Terminal n
Exchange the nth bus terminal
0
Error at initialisation
Exchange Bus Coupler
1
Internal data error
Perform a hardware reset on the Bus Coupler (switch off and
on again)
6
2
DIP switch changed after a
software reset
Perform a hardware reset on the Bus Coupler (switch off and
on again)
7
0
Note: Cycle time was
exceeded
Warning: the set cycle time was exceeded. This indication
(flashing LEDs) can only be cleared by booting the Bus
Coupler again.
Remedy: increase the cycle time
0
Checksum error in Flash
program
Re-transfer the program to the Bus Terminal Controller
9
1
Incorrect or faulty library
implemented
Remove the faulty library
10
n
Bus Terminal n is not
consistent with the
configuration that existed
when the boot project was
created
Check the nth Bus Terminal. The boot project must be deleted
if the insertion of an nth bus terminal is intentional
14
n
nth Bus Terminal has the
wrong format
Start the Bus Coupler again, and if the error occurs again then
exchange the Bus Terminal
15
n
Number of Bus Terminals is
no longer correct
Start the Bus Coupler again. If the error occurs again, restore
the manufacturers setting using the KS2000 configuration
software
16
n
Length of the K-Bus data is
no longer correct
Start the Bus Coupler again. If the error occurs again, restore
the manufacturers setting using the KS2000 configuration
software
LED bus - fieldbus diagnosis
LED
Meaning
LED RUN
no fieldbus connected, Bus Coupler searches for baud rate
LED BF
error flashing - error type - display
LED DIA
Bus Coupler has found baud rate, waiting for config and parameter data
LED RUN
LED BF LED DIA
Meaning
off
off
off
no fieldbus connected, Bus Coupler searches for baud rate
on
on
on
on
on
off
Bus Coupler has found baud rate, waiting for config and parameter data
on
off
off
no error, coupler in data exchange
on
off
flashing
error, see error code